The MCD3000 Soft Starters include a range of
protection functions. Faults identified by these systems
are indicated with a trip code on the Local Control
Panel display. The following section of this manual
explains the trip codes and action required.
Procedures for faults not identified with a trip code are
detailed in the General Faults section.
The voltage of the soft starter is
dangerous whenever the equipment is
connected to the mains. Work on the
equipment should be carried out by
qualified personnel. Before performing any
maintenance and repair work, switch off the electrical
supply to the device and observe all safety regulations.
Trip Codes
When a protection function operates the MCD3000
enters a trip state and displays the following data.
•
The trip LED is illuminated
•
The [CODE] LED is illuminated indicating the
display is showing trip code data
ATTENTION
You can view motor temperature as calculated
by the MCD3000 motor thermal model by
using the [+/-] push buttons to scroll the numeric
display between current [AMPS], temperature [TEMP]
and trip code [CODE].
The trip code data is made up of two parts.
MG.15.A2.22 – VLT is a registered Danfoss trademar
MCD3000 Series
The first digit indicates the trip number. (The
MCD3000 has a trip log that records the last eight trip
events, trip number 1 is the most recent trip. Refer to
the next section of the manual for description of the
Trip Log).
The second digit indicates the cause of the trip
Code
Cause & Action
Shorted SCR trip.
0
The MCD3000 has detected a shorted
SCR.
•
Test the MCD3000 SCRs using the
Power Circuit Test described in the
Test and measurement procedures
chapter later in this section of the
manual.
•
A shorted SCR trip can only be
reset by removing control voltage.
Excess start time trip.
1
The start time has exceed the maximum
limit programmed in Par. 10 Excess
Start Time Protection.
•
Identify and remedy why the motor
is taking longer than normal to
accelerate.
•
Reset the MCD3000
•
Restart the motor.
Overcurrent trip.
2
The motor has experienced an overload
condition that exceeded its thermal
capability as programmed in Par. 6
Motor Thermal Capacity.
•
Identify and correct the cause of the
overload.
•
Wait for the motor to cool
sufficiently to allow a restart.
•
Reset the MCD3000.
•
Restart the motor.
In an emergency situation where it is
critical to immediately restart the motor
and overload protection of the motor is
a secondary concern, the MCD3000
overload protection can be reset by
temporarily removing control supply
voltage.
41
-
Contents
-
Table of Contents
-
Bookmarks
Quick Links
MG.15.A2.22 — VLT is a registered Danfoss trademar
Section 0.0
Section 1.0
Section 2.0
Section 3.0
Section 4.0
Section 5.0
Section 6.0
Section 7.0
Section 8.0
MCD3000 Series
…………………………………………………… 3
…………………………………………….. 4
……………………………………………….. 5
Installation
3.2 Ventilation ……………………………………………….. 7
5.4 Restart Delay …………………………………………. 29
Specifications
7.9 Soft Braking …………………………………………… 39
8.1 Trip Codes …………………………………………….. 41
1
Summary of Contents for Danfoss MCD3000 Series
MCD3000 Series
MG.15.A2.22 – VLT is a registered Danfoss trademar
1
Contents
Section 0.0
■
Warnings
…………………………..………………………. 3
Section 1.0
■
Quick Set-up
…………………………..………………… 4
Section 2.0
■
Description
…………………………..…………………… 5
Section 3.0
■
Installation
3.1
Mechanical Installation …………………………..….. 7
3.2 Ventilation …………………………..…………………… 7
3.3 General Layout …………………………..……………. 8
3.4 Power Wiring — Standard Connection ……………. 8
3.5 Power Wiring — Bypass Connection ………………. 8
3.6 Power Wiring — D.C.Brake Connection ………….. 9
3.7 Control Supply Voltage …………………………..…. 9
3.8 Control Wiring …………………………..……………. 10
3.9 Motor Thermistors …………………………..……… 10
3.10 Control Circuit Examples ………………………… 11
3.11 Serial Communications ………………………….. 13
Section 4.0
■
Programming
4.1
Programming Procedure ………………………….. 16
4.2 Programmable Functions …………………………. 17
Section 5.0
■
Operation
5.1
Local Control Panel …………………………..…….. 28
5.2 Remote Control …………………………..…………. 29
5.3 Serial Communications ………………………….... 29
5.4 Restart Delay …………………………..…………….. 29
5.5 Secondary Parameter Set ………………………… 29
5.6 Motor Thermal Model …………………………..….. 29
5.7 Pre-start Tests …………………………..…………… 29
5.8 Operation After Power Loss ……………………… 29
Section 6.0
■
Specifications
6.1
General Technical Data ………………………….... 30
6.2 Current Ratings …………………………..………….. 31
6.3 Power Termination Details ……………………….. 32
6.4 Semi-conductor Fuses …………………………..… 32
6.5 Dimensions/Weights …………………………..…… 33
Section 7.0
■
Design Guide
7.1
Reduced Voltage Starting ………………………… 34
7.2 Types Of Soft Start Control ………………………. 35
7.3
MCD3000 Control Principles …………………….. 35
7.4 Understanding Soft Starter Ratings ……………. 36
7.5 Model Selection …………………………..…………. 36
7.6 Typical Applications …………………………..……. 38
7.7 Power Factor Correction ………………………….. 39
7.8 Line Contactors …………………………..…………. 39
7.9 Soft Braking …………………………..………………. 39
Section 8.0
■
Fault Procedure
8.1
Trip Codes …………………………..………………… 41
Specifications:950/950684-mcd3000_series.pdf file (05 Mar 2023) |
Accompanying Data:
Danfoss MCD3000 Series Controller PDF Manual (Updated: Sunday 5th of March 2023 06:57:38 PM)
Rating: 4.8 (rated by 31 users)
Compatible devices: AVT/VG, AK-PC 772A, AME 130, VLT AutomationDrive FC 302, DEVIreg Multi, EFIT 850, Link CC, EKC 102C.
Recommended Documentation:
Text Version of Danfoss MCD3000 Series Manual
(Ocr-Read Summary of Contents, UPD: 05 March 2023)
-
35, MCD3000 Series MG.15.A2.22 – VLT is a registered Danfoss trademar 35 Design Guide generated in the resistors during a start. A long cool down period is required between starts. 3. Poor performance for heavy duty or extended starts because heat build up …
-
18, MCD3000 Series ✭ = factory setting 18 MG.15.A2.22 – VLT is a registered Danfoss trademark Programming 2. On generator set supplies where a gradual increase in current is required to allow greater time for the generator set to respond to the increased lo…
-
9, MCD3000 Series MG.15.A2.22 – VLT is a registered Danfoss trademar 9 Installation Either Relay Output C or Relay Output A can be programmed to control operation of the bypass contactor. Par. 36 Relay A — Function Assignment = 1 (Run) Par. 38 Relay C — Function Assignment = 0 (Run) Failure to corr…
-
43, Danfoss MCD3000 Series MCD3000 Series MG.15.A2.22 – VLT is a registered Danfoss trademar 43 Fault Procedure ■ Trip Log When the MCD3000 enters a trip state, the cause of the trip is recorded in a trip log. The trip log records the cause of the last eight trip events. Each trip event is numbered…
-
21, MCD3000 Series ✭ = factory setting MG.15.A2.22 – VLT is a registered Danfoss trademar 21 Programming motor deceleration is monitored and soft stop operation is automatically adjusted to optimise performance. Enhanced pump control may however o…
-
42, MCD3000 Series 42 MG.15.A2.22 – VLT is a registered Danfoss trademark Fault Procedure Code Cause & Action 3 Motor thermistor trip. Thermistors in the motor have indicated an overtemperature state. • Identify and correct the cause of the motor …
-
22, MCD3000 Series ✭ = factory setting 22 MG.15.A2.22 – VLT is a registered Danfoss trademark Programming technique described in the Design Guide section of this manual. 20 Local / Remote Mode Value: 0 — 3 ✭ 0 ([LOCAL/REMOTE] button enabled) 0 = [Local/R…
-
5, Danfoss MCD3000 Series MCD3000 Series MG.15.A2.22 – VLT is a registered Danfoss trademar 5 Description ■ Description The Danfoss MCD3000 Soft Starter is an advanced electronic motor starting system. It performs four main functions; 1. Start control. 2. Stop control, including both soft stop (extended stop time) and brak…
-
34, Danfoss MCD3000 Series MCD3000 Series 34 MG.15.A2.22 – VLT is a registered Danfoss trademark Design Guide ■ Design Guide This section provides data useful in the selection and application of soft starters. ■ Reduced voltage starting When started under full voltage conditions a.c.induction motors initially draw Lo…
-
6, MCD3000 Series 6 MG.15.A2.22 – VLT is a registered Danfoss trademark Description ■ Functions Function Related Parameters Starting • Current Limit • Current Ramp • Torque Boost 2 3 & 4 16 Stopping • Soft Stop • Pump Control • D.C. Brake…
-
Danfoss MCD3000 Series User Manual
-
Danfoss MCD3000 Series User Guide
-
Danfoss MCD3000 Series PDF Manual
-
Danfoss MCD3000 Series Owner’s Manuals
Recommended Instructions: Calgary CD30, MAC Viper AirFX, AB RESISTER
-
Crestron onCue BPC-8
1quickstart guide BPC-8www.crestron.com888.273.7876 201.767.3400©2011 Specifications subject to change without notice. BPC-8For details, refer to the latest version of theBPC-8 Operations & Installation Guide, Doc. 7100.QUICKSTART DOC. 7101B (2029036) 02.11onCue™ Basic Presentation ControllerAll brand names, product names, and trademarks are the property of their respec …
onCue BPC-8 2
-
YASKAWA SI-T3 MECHATROLINK-II A1000 Series
MECHATROLINK-II 通信安川1000シリーズオプション取扱説明書形 式SI-T3MECHATROLINK-IIYASKAWA 1000-Series OptionInstallation ManualType: SI-T3To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual.製品を安全にお使い頂くために,本書を …
SI-T3 MECHATROLINK-II A1000 Series 32
-
RBI FUTERA XLF Series
Copyright 2019 Mestek, Inc. Futera III Boiler manual or Futera Fusion Boiler manual or Futera XLF Boiler manual This manual is intended only for use by a qualified heating installer/technician. Read and follow this manual, all supplements and related instructional information provided with the boiler. Install, start and service the boiler only in the sequence and meth …
FUTERA XLF Series 128
-
Dynojet Power commander III
i105-411 2000-2001 Honda RC51 — PCIII USB — 12000-2001 Honda RC51Installation InstructionsDynojet Research 2191 Mendenhall Drive North Las Vegas, NV 89031 (800) 992-4993 www.powercommander.comParts List1 Power Commander1 USB Cable1 CD-ROM1 Installation Guide1 Power Adapter2 Power Commander Decals2 Dynojet Decals1 Velcro®Strip1 Alcohol SwabYou can also d …
Power commander III 3
Additional Information:
Popular Right Now:
Operating Impressions, Questions and Answers:
Предложите, как улучшить StudyLib
(Для жалоб на нарушения авторских прав, используйте
другую форму
)
Ваш е-мэйл
Заполните, если хотите получить ответ
Оцените наш проект
1
2
3
4
5