Dkg 972 n mod 21 ошибки

Gas Burner Safety Control DKG 972

For 2-stage atmospheric gas burners

Flame detection:

— Ionisation probe

— Infrared-flicker detector IRD 1020.1

— UV flame sensor UVD 971

INTRODUCTION

The burner control box DKG 972 controls and supervises

atmospheric burners for gas. They are approved and certified

according to the applicable European standards and

regulations.

The microprocessor-based programming sequence ensu-

res extremely stable timings independent of voltage varia-

tions, ambient temperature and/or switch-on cycles. The

built-in information system not only provides a continuous

monitoring of the actual state of the box (very helpful es-

pecially for monitoring the start-up phase) but also informs

about the cause of a possible lock out. The lock out cause

is stored in such a way that it can be retrieved even after a

power failure.

The control box is designed for maximum safety in case of

fluctuations in the voltage supply. If the mains voltage drops

below the permitted level, operation is interrupted and the

control box automatically prevents the start sequence from

being repeated. In this way, the safety of the system is not

put at risk by a drop in the mains voltage. This low-voltage

protection works not only during start-up but also perma-

nently during operation.

CONSTRUCTIONAL FEATURES

The control box circuitry is protected by a flame resistant,

transparent plug-in type plastic housing. A central fixing

screw locks the control box to the wiring base.

The plug-in control box incorporates the microprocessor

based timer, flame check and reset circuits.

Manual reset from lock out and set to lock out is provided by

a push button with an integrated LED information system.

A variety of cable entry points provides complete flexibility

for electrical wiring.

The wiring base S98 is equipped with spare- and extraterminals

and allows together with a variety of cable entry points utmost

flexibility of electrical wiring.

The DKG 972 are compatible with the TFI 812.

Different are only the pre- and post-ignition times.

Max. heating power according the limits in the Gas Appliance

Directive.

Table of timings (sec.)

Model

waiting time start

tw

05

12

10

12

pre-ignition time

Stray light monitoring

tvz

3

3

TECHNICAL DATA

Operating voltage

or

Fuse rating

Power consumption

Max. load per output

— term. 3 ignition trafo

— term. 5 + 6 solenoid valves

— term. 7 alarm indicator

— term. 4 auxiliary blower

total load

Reset time from lock out

Re-cycling / repetition (max. 4x) after a loss-of-flame during

operation

Sensitivity

min. ionisation current required

Sensitivity for stray light

Ionisation probe insulation

Stray capacitance

max. cable length

Flame detectors

IRD 1020.1

UVD 971

Weight incl. Wiring base

Mounting position

Protection class

Approved ambient parameter

for control and flame detector

— for operation

— for storage

Build-up of ice, penetration of

water and condensing water are

Approvals according

to European standards

Classified acc. to EN 298

safety time

tf

ts

5

5

5

10

1

220 / 240 V (-15… +10%)

50 Hz (±5%)

110 / 120 V (-15… +10%)

60 Hz (±5%)

10 A fast, 6 A slow

ca. 12 VA

1.0 A, cos ϕ 0.2

0.5 A, cos ϕ 0.4

0.5 A, cos ϕ 0.4

2.0 A, cos ϕ 0.4

4.0 A, cos ϕ 0.4

max. 16 A during 0,5 sec

none

1 µA

1.5 µA

0.4 µA

probe — earth

greater than 50 MΩ

probe- earth

less then 1000 pF

< 3 m

side-on or end-on viewing

end-on viewing

190 g

any

IP 40

max. 95% at 30° C

-20° C… +60° C

-20° C… +80° C

inadmissible

EN 298 and EN 230, as

well as all other relevant

Directives and standards

ATLLXN

post-ignition time

delay 2nd-stage

tn

tv2

4

25

9

25

Gas Burner Safety Control DKG 972

For 2-stage atmospheric gas burners

Flame detection:

— Ionisation probe

— Infrared-flicker detector IRD 1020.1

— UV flame sensor UVD 971

INTRODUCTION

The burner control box DKG 972 controls and supervises

atmospheric burners for gas. They are approved and certified

according to the applicable European standards and

regulations.

The microprocessor-based programming sequence ensu-

res extremely stable timings independent of voltage varia-

tions, ambient temperature and/or switch-on cycles. The

built-in information system not only provides a continuous

monitoring of the actual state of the box (very helpful es-

pecially for monitoring the start-up phase) but also informs

about the cause of a possible lock out. The lock out cause

is stored in such a way that it can be retrieved even after a

power failure.

The control box is designed for maximum safety in case of

fluctuations in the voltage supply. If the mains voltage drops

below the permitted level, operation is interrupted and the

control box automatically prevents the start sequence from

being repeated. In this way, the safety of the system is not

put at risk by a drop in the mains voltage. This low-voltage

protection works not only during start-up but also perma-

nently during operation.

CONSTRUCTIONAL FEATURES

The control box circuitry is protected by a flame resistant,

transparent plug-in type plastic housing. A central fixing

screw locks the control box to the wiring base.

The plug-in control box incorporates the microprocessor

based timer, flame check and reset circuits.

Manual reset from lock out and set to lock out is provided by

a push button with an integrated LED information system.

A variety of cable entry points provides complete flexibility

for electrical wiring.

The wiring base S98 is equipped with spare- and extraterminals

and allows together with a variety of cable entry points utmost

flexibility of electrical wiring.

The DKG 972 are compatible with the TFI 812.

Different are only the pre- and post-ignition times.

Max. heating power according the limits in the Gas Appliance

Directive.

Table of timings (sec.)

Model

waiting time start

tw

05

12

10

12

pre-ignition time

Stray light monitoring

tvz

3

3

TECHNICAL DATA

Operating voltage

or

Fuse rating

Power consumption

Max. load per output

— term. 3 ignition trafo

— term. 5 + 6 solenoid valves

— term. 7 alarm indicator

— term. 4 auxiliary blower

total load

Reset time from lock out

Re-cycling / repetition (max. 4x) after a loss-of-flame during

operation

Sensitivity

min. ionisation current required

Sensitivity for stray light

Ionisation probe insulation

Stray capacitance

max. cable length

Flame detectors

IRD 1020.1

UVD 971

Weight incl. Wiring base

Mounting position

Protection class

Approved ambient parameter

for control and flame detector

— for operation

— for storage

Build-up of ice, penetration of

water and condensing water are

Approvals according

to European standards

Classified acc. to EN 298

safety time

tf

ts

5

5

5

10

1

220 / 240 V (-15… +10%)

50 Hz (±5%)

110 / 120 V (-15… +10%)

60 Hz (±5%)

10 A fast, 6 A slow

ca. 12 VA

1.0 A, cos ϕ 0.2

0.5 A, cos ϕ 0.4

0.5 A, cos ϕ 0.4

2.0 A, cos ϕ 0.4

4.0 A, cos ϕ 0.4

max. 16 A during 0,5 sec

none

1 µA

1.5 µA

0.4 µA

probe — earth

greater than 50 MΩ

probe- earth

less then 1000 pF

< 3 m

side-on or end-on viewing

end-on viewing

190 g

any

IP 40

max. 95% at 30° C

-20° C… +60° C

-20° C… +80° C

inadmissible

EN 298 and EN 230, as

well as all other relevant

Directives and standards

ATLLXN

post-ignition time

delay 2nd-stage

tn

tv2

4

25

9

25

Содержание

  1. Honeywell DKG 972-N mod.10
  2. Тема: honeywell DKG-972 задумки
  3. honeywell DKG-972 задумки
  4. Honeywell DKG972-N опознать стабилитроны
  5. Неисправности газовых котлов Ремонт газовых котлов Диагностика газовых котлов Схемы и инструкции Марки и модели котлов Популярные темы
  6. Неисправности
  7. Ремонт газовых котлов и колонок
  8. Диагностика газовых котлов
  9. Где скачать схему газового котла ?
  10. Какие марки рассмотрены
  11. Популярные темы
  12. Тема: honeywell DKG-972 задумки
  13. honeywell DKG-972 задумки
  14. Блок управления горением Honeywell DKG 972-N
  15. Особенности блока управления Honeywell:

Honeywell DKG 972-N mod.10

Honeywell Satronic DKG972-N mod.10 предназначены для контроля и управления работой газовых горелок, дизельных горелок,теплогенераторов, газовых котлов

Для 2-х ступенчатых атмосферных газовых горелок

Особенности Satronic DKG 972-N mod.10:

— Программирование последовательности операций с помощью DKG972-N mod.10 гарантирует высочайшую стабильность розжига независимо от колебаний напряжения, окружающей температуры и/или циклов включения.

— Встроенная информационная система не только обеспечивает непрерывный контроль реального состояния устройства (что особенно важно для мониторинга фазы запуска), но сообщает о причине возможного автоматического отключения.

— Информация о причине отключения записывается в энергонезависимой памяти.

— Автомат розжига обеспечивает максимальную безопасность в случае колебания напряжения электросети. Если напряжение питания упадет ниже допустимого уровня, то операция прерывается и автомат блокирует повторную попытку запуска. Эта защита от падения напряжения действует не только при запуске, но и постоянно во время операций.

— Защелкивающийся прозрачный корпус из огнеупорной пластмассы, крепится на монтажной плате фиксирующим винтом.

— В корпусе автомата размещены микропроцессорный таймер, детектор пламени и электросхемы сброса.

— Кнопка со встроенным светодиодом предназначена для блокировки и ручного сброса при блокировке.

В случае неисправности светодиод зажигается и горит немигающим светом. Каждые 10 секунд это освещение прерывается флэш-кодом, указывающим причину ошибки, поэтому до сброса повторно выполняется следующая последовательность.

Источник

Тема: honeywell DKG-972 задумки

Опции темы
Оценка этой темы
Отображение

honeywell DKG-972 задумки

Добрый день . Есть котел водогрейный-ROSSEN. автоматика собрана на honeywell DKG-972.Все хорошо. было бы. Если котел не отключался после набора температуры. При недостаче температуры котел переходит на большое пламя. когда достигается заданная температура происходит переход на малое пламя. если и дальше происходить набор температуры происходить полное отключение. Это не хорошо. было бы лучше если котел оставался на растопочной горелке. Потому что в основном сбой происходят при розжиге горелки.Надо бы оставить растопочную горелку, но не могу оставить защиту по пламени для растопочной горелки.подумаем вместе ,как это можно сделать.

Обратиться с претензией к производителю.

Ваш покорный слуга делал всевозможные доработки автоматики таких котлов. Вот, например: http://kotelna.tk/index.php?put=1-1-7-18 (внизу страницы)

Последний раз редактировалось Stentor; 02.07.2020 в 18:59 .

Кажется, я понял, в чём дело. Там есть и регулирующее реле температуры, выключающее горелку, и аварийное?
Наверное, изготовитель котла поместил контакты регулирующего реле температуры, выключающего горелку, в цепь электропитания «топочного автомата»:

. А по логике, это реле должно размыкать только электропитание газовых клапанов.

Последний раз редактировалось Stentor; 02.07.2020 в 18:58 .

Это обман потребителя. Автомат горения одноступенчатый, первая ступень предназначена только для розжига, чтобы не было хлопка.
Автомат горения для двухступенчатых горелок должен управляться двумя термостатами, первой и второй ступени. Здесь и предельный, и регулирующий термостаты тупо рвут питание автомата. Различие только в том, что предельный термостат с блокировкой.
Ничего здесь сделать нельзя.

Надо просто пару проводов перебросить.

Последний раз редактировалось Stentor; 02.07.2020 в 18:58 .

Уверены, что получится? Не будет аварии по пламени на малом горении? Производитель до этого не додумался?

Не додумался? А много ли он думал?
Да там в схеме ошибки прямо в глаза бросаются.

Последний раз редактировалось Stentor; 02.07.2020 в 18:57 .

Screenshot_2019-09-22-17-33-05-041.jpeg
5.6.1. Принципиальные электрические схемы котлов RSA
А1 — 2ТРМ1, A2 — DKG 972, FU — предохранитель 2А, SА1 — выключатель «Сеть», SK1 — предельный термостат (перегрев
теплоносителя), SK2 — предельный термостат (тяга).
Рисунок 32. Принципиальная электрическая схема котлов RS-A150, RS-A200
Здесь установлен третий клапан, на большое горение, управляемый термостатом второй ступени, в качестве которого применён 2ТРМ1.

Последний раз редактировалось Eugene.A; 22.09.2019 в 17:38 .

пока меня тут не было уйму постов накидали. Это уже хорошо.
Конечно. разработчикам все по фиг. им бы только котел отключался по любому случаю. Было бы и то большим плюсом. если бы они на этот котел поставили нормальный трансформатор розжига,а не эту игрушку от бытового котла.
Ладно а теперь к вопросу. Хорошо что ещё Eugene.A схему залил. По схеме видим что второй выход ТРМ командует с большим и малым пламенем. Если цепь есть идет большое горение если нет то остается только малое. А вот первый выход ТРМ дает разрешение котлу работать до предельный температуры. Которую мы сами же задаем. Это предел рабочей температуры. а аварийный предел контролируется с термостатом. И так если разрывается цепь на первом выходе ТРМ на 9 ую клемму контроллера перестает поступать напряжение. И котел уходить в режим ожидания. Меня интересует что там внутри контроллера твориться за этой 9 ой клеммой?

Источник

Honeywell DKG972-N опознать стабилитроны

Доброе время суток ,Ребята ,может кому попадался такой блок розжига с Buderusa ,Прошу узнать номиналы стабилитронов D4.иD5.
Блок работает .НО стабилитроны поставил от балды.

Неисправности газовых котлов Ремонт газовых котлов Диагностика газовых котлов Схемы и инструкции Марки и модели котлов Популярные темы

Неисправности

Этот блок для тех, кто впервые попал на страницы нашего сайта. В нашем форуме рассмотрены различные неисправности встречающиеся в газовых котлах и колонках. Наиболее частое проявление дефектов следующие:

  • не включается
  • тухнет газовая горелка
  • не набирает температуру
  • не выполняет команды управления
  • слабое пламя
  • свист и шум в котле
  • в системе холодная вода
  • проблема циркуляционного насоса

Многие неисправности являются не причиной, а следствием другой неисправности. Подробную информацию Вы найдете в разделе ремонта газового оборудования.

Ремонт газовых котлов и колонок

Учитывайте, что ремонт газового оборудования и монтаж отопления должны выполнять профессиональные, сертифицированные работники. На форуме размещены темы рассчитанные на мастеров в этой области. Неквалифицированный ремонт может иметь очень серьёзные последствия. В форуме рассматриваются следующие вопросы:

  • Диагностика
  • Определение неисправности
  • Методы ремонта
  • Поиск запчастей
  • Обслуживание
  • Установка и настройка
  • Диагностика газовых котлов

    Как правило, большинство современных газовых котлов имеют внутреннюю систему диагностики, которая самостоятельно выявляет какую-либо неисправность и высвечивает ее код на цифровом дисплее. Так как каждая модель имеет свои коды, они перечислены не здесь, а в соответствующих темах форума

    Из кодов ошибок мастер выявляет наиболее вероятную причину поломки. Однако некоторые дефекты процессор (контроллер) не определяет в кодах ошибок, они требуют детальных ручных измерений или настройки узлов оборудования. По результатам диагностики возможно потребуется:

    • Замена отдельных компонентов
    • Замена платы в сборе
    • Замена узлов
    • Настройка узлов
  • Где скачать схему газового котла ?

    Начинающие ремонтники часто ищут принципиальные схемы, схемы соединений, пользовательские и сервисные инструкции. На сайте они размещены в специально отведенных разделах и доступны к скачиванию гостям, либо после создания аккаунта:

    • Файлы для ремонта газовых котлов
    • Запросы схем и прошивок

    Многие файлы (схемы, прошивки, инструкции) отображаются и доступны только принятым в группу профессионального ремонта. Для их просмотра и доступа к ним, регистрации аккаунта не достаточно. При отстутствии на сайте необходимой схемы и прочей документации, участники запрашивают ее в соответствующем разделе.

    Какие марки рассмотрены

    В форуме рассмотрены практически все используемые марки котлов.
    Собрана большая база по неисправностям, методам их диагностики и устранения. Приведем несколько ссылок:

    Популярные темы

    В процессе ремонта у мастеров возникают интересные темы для обсуждения. Перечислим только некоторые:

    Источник

    Тема: honeywell DKG-972 задумки

    Опции темы
    Оценка этой темы
    Отображение

    honeywell DKG-972 задумки

    Добрый день . Есть котел водогрейный-ROSSEN. автоматика собрана на honeywell DKG-972.Все хорошо. было бы. Если котел не отключался после набора температуры. При недостаче температуры котел переходит на большое пламя. когда достигается заданная температура происходит переход на малое пламя. если и дальше происходить набор температуры происходить полное отключение. Это не хорошо. было бы лучше если котел оставался на растопочной горелке. Потому что в основном сбой происходят при розжиге горелки.Надо бы оставить растопочную горелку, но не могу оставить защиту по пламени для растопочной горелки.подумаем вместе ,как это можно сделать.

    Обратиться с претензией к производителю.

    Ваш покорный слуга делал всевозможные доработки автоматики таких котлов. Вот, например: http://kotelna.tk/index.php?put=1-1-7-18 (внизу страницы)

    Последний раз редактировалось Stentor; 02.07.2020 в 18:59 .

    Кажется, я понял, в чём дело. Там есть и регулирующее реле температуры, выключающее горелку, и аварийное?
    Наверное, изготовитель котла поместил контакты регулирующего реле температуры, выключающего горелку, в цепь электропитания «топочного автомата»:

    . А по логике, это реле должно размыкать только электропитание газовых клапанов.

    Последний раз редактировалось Stentor; 02.07.2020 в 18:58 .

    Это обман потребителя. Автомат горения одноступенчатый, первая ступень предназначена только для розжига, чтобы не было хлопка.
    Автомат горения для двухступенчатых горелок должен управляться двумя термостатами, первой и второй ступени. Здесь и предельный, и регулирующий термостаты тупо рвут питание автомата. Различие только в том, что предельный термостат с блокировкой.
    Ничего здесь сделать нельзя.

    Надо просто пару проводов перебросить.

    Последний раз редактировалось Stentor; 02.07.2020 в 18:58 .

    Уверены, что получится? Не будет аварии по пламени на малом горении? Производитель до этого не додумался?

    Не додумался? А много ли он думал?
    Да там в схеме ошибки прямо в глаза бросаются.

    Последний раз редактировалось Stentor; 02.07.2020 в 18:57 .

    Screenshot_2019-09-22-17-33-05-041.jpeg
    5.6.1. Принципиальные электрические схемы котлов RSA
    А1 — 2ТРМ1, A2 — DKG 972, FU — предохранитель 2А, SА1 — выключатель «Сеть», SK1 — предельный термостат (перегрев
    теплоносителя), SK2 — предельный термостат (тяга).
    Рисунок 32. Принципиальная электрическая схема котлов RS-A150, RS-A200
    Здесь установлен третий клапан, на большое горение, управляемый термостатом второй ступени, в качестве которого применён 2ТРМ1.

    Последний раз редактировалось Eugene.A; 22.09.2019 в 17:38 .

    пока меня тут не было уйму постов накидали. Это уже хорошо.
    Конечно. разработчикам все по фиг. им бы только котел отключался по любому случаю. Было бы и то большим плюсом. если бы они на этот котел поставили нормальный трансформатор розжига,а не эту игрушку от бытового котла.
    Ладно а теперь к вопросу. Хорошо что ещё Eugene.A схему залил. По схеме видим что второй выход ТРМ командует с большим и малым пламенем. Если цепь есть идет большое горение если нет то остается только малое. А вот первый выход ТРМ дает разрешение котлу работать до предельный температуры. Которую мы сами же задаем. Это предел рабочей температуры. а аварийный предел контролируется с термостатом. И так если разрывается цепь на первом выходе ТРМ на 9 ую клемму контроллера перестает поступать напряжение. И котел уходить в режим ожидания. Меня интересует что там внутри контроллера твориться за этой 9 ой клеммой?

    Источник

    Блок управления горением Honeywell DKG 972-N

    Цена указана за модификацию DKG 972-N Mod 21. Стоимость других модификаций уточняйте у менеджеров.

    Honeywell DKG 972-N разработан под двухступенчатые атмосферные горелки и воздухонагреватели. Используют совместно с блоком датчики: инфракрасный IRD1020, ультрафиолетовый UVD971, а также ионизационный электрод. Устройство обеспечивает безопасность системы во время всего цикла работы.

    Особенности блока управления Honeywell:

    • Сертификация по европейским стандартам.
    • Блокирует горелку при неисправностях при достижении безопасного времени.
    • Есть возможность передачи данных с блока на ПК.
    • Возможность энергонезависимой блокировки.

    Конструкция блока Honeywell представляет собой взрывозащищенный пластиковый корпус вставного типа с микропроцессором и другими электронными компонентами на печатной плате. В верхней части корпуса устройства Honeywell расположены информационные светодиоды. Микропроцессор позволяет достигнуть стабильного времени работы независимо от колебаний напряжения и температур.

    Информационная система блока управления горением Honeywell обеспечивает постоянный мониторинг происходящих процессов и предоставляет коды возможных ошибок. Код восстанавливает даже при падении напряжения. Система не подвергается опасности даже при резком падении напряжения.

    Источник

    1. nafsinai

      Регистрация:
      17.03.19
      Сообщения:


      3

      Благодарности:
      0

      nafsinai

      Новичок

      Регистрация:
      17.03.19
      Сообщения:
      3
      Благодарности:
      0

      Buderus Logano G234X (WS) + Logamatic 2109, сгорел Автомат горения DKG 972-N Mod. 21

      Уважаемы специалисты не могли бы Вы дать совет, суть вопроса в чем, год назад установил в частные дом газовый котел Buderus Logano G234X (WS) -60kw с системой управления Logamatic 2109 работало все без нареканий, не давно начались скачки напряжения, после чего котел перестал работать (к дому подведена только 1 фаза, и стоит стабилизатор напряжения РЕСАНТА спн 13500 вход 90-260B, реле-прерывателей нет) Посмотрев систему управления Logamatic выяснил, что все предохранители в целости и сохранности, покопавшись дальше, увидел следы копати на автомате горения, сгорел варистор, выпаяв его результата не дало, котел не запустился, не найдя подробной схемы автомата горения мои скудные знания на этом иссякли я не стал копаться в нем дальше, и заказал новый автомат горения DKG 972-N Mod. 21. После установки нового автомата горения, котел снова заработал. Но вчера произошло опять скачек напряжения, при том что напряжение полностью отключилось и резко появилось. Я сразу пошел проверить котел и опять такая же ситуация, только еще хуже автомат горения пришлось буквально выдирать из котла, клемы пришлось выкусывать так как посадочные места просто расплавились, а в самом автомате горения помимо варистора оплавилась сама плата да так, что я ее из защитного корпуса вытащить не смог. После пошел и проверил всю технику в доме и она вся была целая. Почему при стабилизаторе сгорает только сам автомат горения а все остальное остается целым в том числи и все предохранители в котле? Не уж то данная система настолько уязвима к перепадам напряжения.

    2. ГеннадийВС

      Регистрация:
      19.11.13
      Сообщения:


      742

      Благодарности:
      159

      ГеннадийВС

      Живу здесь

      Регистрация:
      19.11.13
      Сообщения:
      742
      Благодарности:
      159
      Адрес:
      Минеральные Воды

      Тут врядли кто даст четкий ответ на причину. Стабилизатор, а тем более Ресанта, не защищает приборы от импульсных помех (скачкообразных) и сам тоже не защищен, отработать их тем более не сможет, предохранители не успеют перегореть, не всегда успеет защитить варистор, есть более быстрые приборы, например супрессоры, а лучше установить на дом устройство молниезащиты соответствующей мощности для вашего дома. Должно присутствоать правильное заземление. Ваш первый блок управления, думаю, возможно восстановить ищите в своем регионе спеца.
      А регион — Россия, шифруемся?

    3. nafsinai

      Регистрация:
      17.03.19
      Сообщения:


      3

      Благодарности:
      0

      nafsinai

      Новичок

      Регистрация:
      17.03.19
      Сообщения:
      3
      Благодарности:
      0

      Просто быстро регистрацию проходил, а так со станицы Тамань Краснодарского края. А по поводу спеца наверное в самом Краснодаре искать нужно, так как сам автомата горения ближайшее только с Москвы заказывать пришлось.

      Да просто быстро регистрацию проходил, а так со станицы Тамань. Краснодарского края. А по поводу спеца наверное где то в Краснодаре искать нужно, так как автомата горения ближайший с Москвы заказывать пришлось. Сам котел в Краснодаре покупался в еще в 2014 и гарантия уже не действительна(

    4. ГеннадийВС

      Регистрация:
      19.11.13
      Сообщения:


      742

      Благодарности:
      159

      ГеннадийВС

      Живу здесь

      Регистрация:
      19.11.13
      Сообщения:
      742
      Благодарности:
      159
      Адрес:
      Минеральные Воды

      Есть в ваших краях люди способные восстановить. Знаю в Сочах, читал были и ближе. Клич брось, мож кто отзовется. Я с таким блоком не возился, начинать не хочется. Думаютебе, еще клапан надо проверять.

    5. ГеннадийВС

      Регистрация:
      19.11.13
      Сообщения:


      742

      Благодарности:
      159

      ГеннадийВС

      Живу здесь

      Регистрация:
      19.11.13
      Сообщения:
      742
      Благодарности:
      159
      Адрес:
      Минеральные Воды

      Котлы нужно покупать те которые распространены в вашем регионе, и развита сеть сервиса, во многих местах продают зч, не гнаться за брендом и не слушать продавца во все уши… .

    6. dxpoha

      Регистрация:
      20.09.10
      Сообщения:


      2.795

      Благодарности:
      877

      dxpoha

      Живу здесь

      Регистрация:
      20.09.10
      Сообщения:
      2.795
      Благодарности:
      877
      Адрес:
      Самара

      Стаб поменять. Ставь штиль is 550.

    7. Партизан32

      Регистрация:
      13.11.18
      Сообщения:


      3.762

      Благодарности:
      1.641

      Партизан32

      Живу здесь

      Регистрация:
      13.11.18
      Сообщения:
      3.762
      Благодарности:
      1.641
      Адрес:
      Брянск

      Там у вас конец света и зимой и летом. Хотите жить спокойно, поставьте хотя бы РНПП. Стабилизатор — вещь бесполезная в вашем случае.

      Да и Анапы хватит, если поискать.

    8. BoschClimate

      Регистрация:
      28.03.18
      Сообщения:


      134

      Благодарности:
      250

      BoschClimate

      Живу здесь

      Регистрация:
      28.03.18
      Сообщения:
      134
      Благодарности:
      250
      Адрес:
      141400, г.Химки, Вашутинское шоссе, дом 24

      Добрый день!
      Дело в том, что стабилизатор работает в определенном диапазоне напряжений, а также, в зависимости от модели, имеет время реакции. У одних он меньше, у других больше.
      А варистор — это элемент защиты от превышения напряжения, и он срабатывает при напряжении 275В, т. е. это напряжение находится за пределами рабочих параметров Вашего стабилизатора. К тому же отличается время реакции. Типовое значение времени срабатывания варисторов при воздействии перенапряжения составляет не более 25 наносекунд (нс).
      А согласно инструкции к Вашему стабилизатору, его время реакции 5-7 мсек. Поэтому в данном случае говорить о ненадежности оборудования или его уязвимости нельзя — параметры электросети далеко за пределами допустимого напряжения. И это вопрос к поставщику электроэнергии.
      Для дополнительной защиты оборудования, например, можно установить внешний блок с варисторами, как вариант, Теплоком Альбатрос.

    9. nafsinai

      Регистрация:
      17.03.19
      Сообщения:


      3

      Благодарности:
      0

      nafsinai

      Новичок

      Регистрация:
      17.03.19
      Сообщения:
      3
      Благодарности:
      0

      Я уже не знаю что делать… опять заказал новый автомат горения, поставил РНПП после счетчика (только потом пришлось переделывать, и ставить не посредственно перед самим котлом, так как скачки были за 250 В, а ночью за 260 было и постоянные перебои со светом мешали) поставил новый стабилизатор, поставил дополнительное устройство от скачков напряжения, даже установил громоотвод как и советовали, проработало все нормально 4 дня и опять скачек напряжения и опять выгорает только автомат горения на газовом котле. При этом за минуты 3-4 до случившегося я проверял котел и он был выключен так ка работал РНПП, я на срабатывание выставил 250 В приходило 250-255 В, после пошел обедать. Разогревал себе еду в микроволновке и она на доли секунды остановилась и снова запустилась, я сразу в котельную а там только запах гари и выгоренный автомат горения. Опять обошел всю технику в доме и ни одного признака сгорания и выгорания… я не понимаю по чему сгорает только автомат горения, просто не понимаю…

    10. Dmitribir

      Регистрация:
      06.09.16
      Сообщения:


      2.023

      Благодарности:
      1.045

      Dmitribir

      Живу здесь

      Регистрация:
      06.09.16
      Сообщения:
      2.023
      Благодарности:
      1.045
      Адрес:
      Москва и МО Север, Тверская область, Зубцов.

      Попробуйте найти и поставить топочник TFI 812.2, они устанавливались ранее. Переделок никаких не потребуется, все встает на штатные места.

    11. Партизан32

      Регистрация:
      13.11.18
      Сообщения:


      3.762

      Благодарности:
      1.641

      Партизан32

      Живу здесь

      Регистрация:
      13.11.18
      Сообщения:
      3.762
      Благодарности:
      1.641
      Адрес:
      Брянск

      Уважаемый, вы в своём уме ? Какие 250, если 242 должно отключаться. Не, ну если вы хотите, можете 300 поставить и продолжать тут жаловаться.

      Проблема не к форуму, а к энергоснабжающей организации. Им же и счёт выставить надо, за уничтоженное оборудование.

    Описание товара

    Топочный автомат Satronic / Honeywell DKG 972-N Mod.21 артикул 0432021 применяется в составе атмосферных котлов. Функция менеджера горения – контроль и управление двухступенчатыми горелками. Комплектация не включает цоколь. Аппарат успешно протестирован и сертифицирован по европейским нормам.

    Важные параметры:

    • Предохранительное время: 10 секунд.
    • Время перед розжигом: 3 сек.
    • Режим функционирования: прерывистый.
    • Источник электропитания: 220/240 В, 50/60 Гц.

    Особенности:

    Управляет программным обеспечением встроенный микропроцессор. Автомат обеспечивает высокую стабильность запуска, вне зависимости от бросков в сети, циклов включения, эксплуатационной температуры.

    Программа постоянно отслеживает все стадии работы устройства (включая этап запуска), оповещает о причинах аварийного отключения. Благодаря наличию энергонезависимой памяти данные о причинах автовыключения не утрачивается даже при обесточивании автомата.

    SATRONIC DKG имеет встроенную защиту от низкого напряжения, что обеспечивает высокий уровень безопасности при работе горелки. При достижении минимального уровня напряжения в сети, автомат отключается и препятствует повторному запуску до восстановления рабочих параметров электропитания. Автоматическая защита работает постоянно, а не только при запуске горелки.

    Контроль наличия пламени происходит при помощи ионизационного электрода/ УФ-датчика/ инфракрасного детектора.

    Конструкция

    SATRONIC DKG имеет пластиковый огнестойкий корпус, устанавливаемый с щелчком. Для монтажа прибора на цоколь предусмотрен центральный винт. Цоколь не входит в базовый комплект.

    Электрозащита корпуса отвечает стандарту IP40. Внутри размещен датчик пламени, микропроцессор, электросхемы сброса.  

    На корпусе находится кнопка ручной блокировки/ перезапуска со световой индикацией.

    Достоинства:

    • надежное функционирование горелки;
    • самодиагностика неполадок;
    • оповещение о причинах выключения;
    • действенная защита от низкого напряжения;
    • энергонезависимая память;
    • кожух из огнестойкого материала.

    На нашем сайте можно купить топочный автомат Satronic / Honeywell DKG 972-N Mod.21 по приемлемой цене, оформив заказ через виртуальную корзину. Полную информацию об устройстве уточняйте у сотрудника «АНКАС».

    CIRCUIT AND TIMING DIAGRAM DKG 972

    Ph

    max. 10 A fast

    HS

    6 A slow

    1

    2

    3

    4

    5

    V1

    M

    IS

    Z

    N

    IRD- OR UVD CONNECTION

    IRD 1020.1

    UVD 971

    BLOCK DIAGRAM DKG 972

    Oscillator

    µC

    Watchdog

    Reset

    Flame

    amplifier

    RZ

    rz

    1

    3

    4

    ST

    GW

    RT

    EV

    6

    7

    8

    9

    A

    V2

    SA

    tw tf tvz tn ts tv2

    term. 8

    blue

    term. 1

    black

    term. 9

    brown

    Fault display

    Information

    EEPROM

    system

    µC

    RV1

    RV2

    RS

    rs

    rv1

    rv2

    5

    6

    7

    HS

    Mains switch

    GW

    Gas proving switch

    ST

    Limit thermostat

    RT

    Control thermostat

    EV

    External reset and lock out button

    IS

    Ionisation probe

    (IRD 1020.1, UVD 971see separate diagram)

    Z

    Ignition

    V1

    Solenoid valve, 1st-stage

    V2

    Solenoid valve, 2nd-stage

    SA

    External lock out signal

    M

    Auxiliary blower

    tw

    Waiting time

    tf

    Stray light monitoring

    tvz

    Pre-ignition time

    tn

    Post-ignition

    ts

    Safety time

    tv2

    2nd-stage delay

    Reset and

    lock out

    Mains

    monitoring

    Power

    supply

    monitoring

    Power

    supply

    8

    9

    A

    5

    Gas Burner Safety Control DKG 972

    For 2-stage atmospheric gas burners

    Flame detection:

    — Ionisation probe

    — Infrared-flicker detector IRD 1020.1

    — UV flame sensor UVD 971

    INTRODUCTION

    The burner control box DKG 972 controls and supervises

    atmospheric burners for gas. They are approved and certified

    according to the applicable European standards and

    regulations.

    The microprocessor-based programming sequence ensu-

    res extremely stable timings independent of voltage varia-

    tions, ambient temperature and/or switch-on cycles. The

    built-in information system not only provides a continuous

    monitoring of the actual state of the box (very helpful es-

    pecially for monitoring the start-up phase) but also informs

    about the cause of a possible lock out. The lock out cause

    is stored in such a way that it can be retrieved even after a

    power failure.

    The control box is designed for maximum safety in case of

    fluctuations in the voltage supply. If the mains voltage drops

    below the permitted level, operation is interrupted and the

    control box automatically prevents the start sequence from

    being repeated. In this way, the safety of the system is not

    put at risk by a drop in the mains voltage. This low-voltage

    protection works not only during start-up but also perma-

    nently during operation.

    CONSTRUCTIONAL FEATURES

    The control box circuitry is protected by a flame resistant,

    transparent plug-in type plastic housing. A central fixing

    screw locks the control box to the wiring base.

    The plug-in control box incorporates the microprocessor

    based timer, flame check and reset circuits.

    Manual reset from lock out and set to lock out is provided by

    a push button with an integrated LED information system.

    A variety of cable entry points provides complete flexibility

    for electrical wiring.

    The wiring base S98 is equipped with spare- and extraterminals

    and allows together with a variety of cable entry points utmost

    flexibility of electrical wiring.

    The DKG 972 are compatible with the TFI 812.

    Different are only the pre- and post-ignition times.

    Max. heating power according the limits in the Gas Appliance

    Directive.

    Table of timings (sec.)

    Model

    waiting time start

    tw

    05

    12

    10

    12

    pre-ignition time

    Stray light monitoring

    tvz

    3

    3

    TECHNICAL DATA

    Operating voltage

    or

    Fuse rating

    Power consumption

    Max. load per output

    — term. 3 ignition trafo

    — term. 5 + 6 solenoid valves

    — term. 7 alarm indicator

    — term. 4 auxiliary blower

    total load

    Reset time from lock out

    Re-cycling / repetition (max. 4x) after a loss-of-flame during

    operation

    Sensitivity

    min. ionisation current required

    Sensitivity for stray light

    Ionisation probe insulation

    Stray capacitance

    max. cable length

    Flame detectors

    IRD 1020.1

    UVD 971

    Weight incl. Wiring base

    Mounting position

    Protection class

    Approved ambient parameter

    for control and flame detector

    — for operation

    — for storage

    Build-up of ice, penetration of

    water and condensing water are

    Approvals according

    to European standards

    Classified acc. to EN 298

    safety time

    tf

    ts

    5

    5

    5

    10

    1

    220 / 240 V (-15… +10%)

    50 Hz (±5%)

    110 / 120 V (-15… +10%)

    60 Hz (±5%)

    10 A fast, 6 A slow

    ca. 12 VA

    1.0 A, cos ϕ 0.2

    0.5 A, cos ϕ 0.4

    0.5 A, cos ϕ 0.4

    2.0 A, cos ϕ 0.4

    4.0 A, cos ϕ 0.4

    max. 16 A during 0,5 sec

    none

    1 µA

    1.5 µA

    0.4 µA

    probe — earth

    greater than 50 MΩ

    probe- earth

    less then 1000 pF

    < 3 m

    side-on or end-on viewing

    end-on viewing

    190 g

    any

    IP 40

    max. 95% at 30° C

    -20° C… +60° C

    -20° C… +80° C

    inadmissible

    EN 298 and EN 230, as

    well as all other relevant

    Directives and standards

    ATLLXN

    post-ignition time

    delay 2nd-stage

    tn

    tv2

    4

    25

    9

    25

    Gas Burner Safety Control DKG 972

    For 2-stage atmospheric gas burners

    Flame detection:

    — Ionisation probe

    — Infrared-flicker detector IRD 1020.1

    — UV flame sensor UVD 971

    INTRODUCTION

    The burner control box DKG 972 controls and supervises

    atmospheric burners for gas. They are approved and certified

    according to the applicable European standards and

    regulations.

    The microprocessor-based programming sequence ensu-

    res extremely stable timings independent of voltage varia-

    tions, ambient temperature and/or switch-on cycles. The

    built-in information system not only provides a continuous

    monitoring of the actual state of the box (very helpful es-

    pecially for monitoring the start-up phase) but also informs

    about the cause of a possible lock out. The lock out cause

    is stored in such a way that it can be retrieved even after a

    power failure.

    The control box is designed for maximum safety in case of

    fluctuations in the voltage supply. If the mains voltage drops

    below the permitted level, operation is interrupted and the

    control box automatically prevents the start sequence from

    being repeated. In this way, the safety of the system is not

    put at risk by a drop in the mains voltage. This low-voltage

    protection works not only during start-up but also perma-

    nently during operation.

    CONSTRUCTIONAL FEATURES

    The control box circuitry is protected by a flame resistant,

    transparent plug-in type plastic housing. A central fixing

    screw locks the control box to the wiring base.

    The plug-in control box incorporates the microprocessor

    based timer, flame check and reset circuits.

    Manual reset from lock out and set to lock out is provided by

    a push button with an integrated LED information system.

    A variety of cable entry points provides complete flexibility

    for electrical wiring.

    The wiring base S98 is equipped with spare- and extraterminals

    and allows together with a variety of cable entry points utmost

    flexibility of electrical wiring.

    The DKG 972 are compatible with the TFI 812.

    Different are only the pre- and post-ignition times.

    Max. heating power according the limits in the Gas Appliance

    Directive.

    Table of timings (sec.)

    Model

    waiting time start

    tw

    05

    12

    10

    12

    pre-ignition time

    Stray light monitoring

    tvz

    3

    3

    TECHNICAL DATA

    Operating voltage

    or

    Fuse rating

    Power consumption

    Max. load per output

    — term. 3 ignition trafo

    — term. 5 + 6 solenoid valves

    — term. 7 alarm indicator

    — term. 4 auxiliary blower

    total load

    Reset time from lock out

    Re-cycling / repetition (max. 4x) after a loss-of-flame during

    operation

    Sensitivity

    min. ionisation current required

    Sensitivity for stray light

    Ionisation probe insulation

    Stray capacitance

    max. cable length

    Flame detectors

    IRD 1020.1

    UVD 971

    Weight incl. Wiring base

    Mounting position

    Protection class

    Approved ambient parameter

    for control and flame detector

    — for operation

    — for storage

    Build-up of ice, penetration of

    water and condensing water are

    Approvals according

    to European standards

    Classified acc. to EN 298

    safety time

    tf

    ts

    5

    5

    5

    10

    1

    220 / 240 V (-15… +10%)

    50 Hz (±5%)

    110 / 120 V (-15… +10%)

    60 Hz (±5%)

    10 A fast, 6 A slow

    ca. 12 VA

    1.0 A, cos ϕ 0.2

    0.5 A, cos ϕ 0.4

    0.5 A, cos ϕ 0.4

    2.0 A, cos ϕ 0.4

    4.0 A, cos ϕ 0.4

    max. 16 A during 0,5 sec

    none

    1 µA

    1.5 µA

    0.4 µA

    probe — earth

    greater than 50 MΩ

    probe- earth

    less then 1000 pF

    < 3 m

    side-on or end-on viewing

    end-on viewing

    190 g

    any

    IP 40

    max. 95% at 30° C

    -20° C… +60° C

    -20° C… +80° C

    inadmissible

    EN 298 and EN 230, as

    well as all other relevant

    Directives and standards

    ATLLXN

    post-ignition time

    delay 2nd-stage

    tn

    tv2

    4

    25

    9

    25

    Gas Burner Safety Control DKG 972

    For 2-stage atmospheric gas burners

    Flame detection:

    — Ionisation probe

    — Infrared-flicker detector IRD 1020.1

    — UV flame sensor UVD 971

    INTRODUCTION

    The burner control box DKG 972 controls and supervises

    atmospheric burners for gas. They are approved and certified

    according to the applicable European standards and

    regulations.

    The microprocessor-based programming sequence ensu-

    res extremely stable timings independent of voltage varia-

    tions, ambient temperature and/or switch-on cycles. The

    built-in information system not only provides a continuous

    monitoring of the actual state of the box (very helpful es-

    pecially for monitoring the start-up phase) but also informs

    about the cause of a possible lock out. The lock out cause

    is stored in such a way that it can be retrieved even after a

    power failure.

    The control box is designed for maximum safety in case of

    fluctuations in the voltage supply. If the mains voltage drops

    below the permitted level, operation is interrupted and the

    control box automatically prevents the start sequence from

    being repeated. In this way, the safety of the system is not

    put at risk by a drop in the mains voltage. This low-voltage

    protection works not only during start-up but also perma-

    nently during operation.

    CONSTRUCTIONAL FEATURES

    The control box circuitry is protected by a flame resistant,

    transparent plug-in type plastic housing. A central fixing

    screw locks the control box to the wiring base.

    The plug-in control box incorporates the microprocessor

    based timer, flame check and reset circuits.

    Manual reset from lock out and set to lock out is provided by

    a push button with an integrated LED information system.

    A variety of cable entry points provides complete flexibility

    for electrical wiring.

    The wiring base S98 is equipped with spare- and extraterminals

    and allows together with a variety of cable entry points utmost

    flexibility of electrical wiring.

    The DKG 972 are compatible with the TFI 812.

    Different are only the pre- and post-ignition times.

    Max. heating power according the limits in the Gas Appliance

    Directive.

    Table of timings (sec.)

    Model

    waiting time start

    tw

    05

    12

    10

    12

    pre-ignition time

    Stray light monitoring

    tvz

    3

    3

    TECHNICAL DATA

    Operating voltage

    or

    Fuse rating

    Power consumption

    Max. load per output

    — term. 3 ignition trafo

    — term. 5 + 6 solenoid valves

    — term. 7 alarm indicator

    — term. 4 auxiliary blower

    total load

    Reset time from lock out

    Re-cycling / repetition (max. 4x) after a loss-of-flame during

    operation

    Sensitivity

    min. ionisation current required

    Sensitivity for stray light

    Ionisation probe insulation

    Stray capacitance

    max. cable length

    Flame detectors

    IRD 1020.1

    UVD 971

    Weight incl. Wiring base

    Mounting position

    Protection class

    Approved ambient parameter

    for control and flame detector

    — for operation

    — for storage

    Build-up of ice, penetration of

    water and condensing water are

    Approvals according

    to European standards

    Classified acc. to EN 298

    safety time

    tf

    ts

    5

    5

    5

    10

    1

    220 / 240 V (-15… +10%)

    50 Hz (±5%)

    110 / 120 V (-15… +10%)

    60 Hz (±5%)

    10 A fast, 6 A slow

    ca. 12 VA

    1.0 A, cos ϕ 0.2

    0.5 A, cos ϕ 0.4

    0.5 A, cos ϕ 0.4

    2.0 A, cos ϕ 0.4

    4.0 A, cos ϕ 0.4

    max. 16 A during 0,5 sec

    none

    1 µA

    1.5 µA

    0.4 µA

    probe — earth

    greater than 50 MΩ

    probe- earth

    less then 1000 pF

    < 3 m

    side-on or end-on viewing

    end-on viewing

    190 g

    any

    IP 40

    max. 95% at 30° C

    -20° C… +60° C

    -20° C… +80° C

    inadmissible

    EN 298 and EN 230, as

    well as all other relevant

    Directives and standards

    ATLLXN

    post-ignition time

    delay 2nd-stage

    tn

    tv2

    4

    25

    9

    25

    Страница 1 из 3

    1. Grixak

      Регистрация:
      28.11.13
      Сообщения:


      24

      Благодарности:
      0

      Grixak

      Участник

      Регистрация:
      28.11.13
      Сообщения:
      24
      Благодарности:
      0
      Адрес:
      Москва

      Ошибка и отключение котла Buderus Logano

      Добрый вечер!
      Переодически котел Buderus Logano G334 с автоматикой Logomax 4211 останавливается и не запускается.
      Нажимаю кнопки на устройствах Honeywell DKG 972-N и котел запускается, работает от нескольких дней до недели и опять останавливается.
      Такая ситуация происходит с начала момента эксплуатации котла (3 года).
      Что делать, велика опасность разморозить систему отопления.
      Спасибо.

    2. Mijjgan

      Регистрация:
      10.04.12
      Сообщения:


      22.974

      Благодарности:
      18.015

      Mijjgan

      Супер-Модератор

      Регистрация:
      10.04.12
      Сообщения:
      22.974
      Благодарности:
      18.015
      Адрес:
      Россия, Москва

      А проверьте фазировку на всякий случай. Уж больно симптомы похожи.

    3. Dmitribir

      Регистрация:
      06.09.16
      Сообщения:


      2.023

      Благодарности:
      1.045

      Dmitribir

      Живу здесь

      Регистрация:
      06.09.16
      Сообщения:
      2.023
      Благодарности:
      1.045
      Адрес:
      Москва и МО Север, Тверская область, Зубцов.

      Так когда на топочнике кнопку нажимаете она красненьким светится или нет?

    4. Andross

      Регистрация:
      29.11.13
      Сообщения:


      120

      Благодарности:
      33

      Andross

      Живу здесь

      Регистрация:
      29.11.13
      Сообщения:
      120
      Благодарности:
      33
      Адрес:
      Воскресенск

      А не замечали, когда чаще останавливается? Ночью или днём? При похолодании или потеплении? Какая ситуация с газом? Какая схема газоснабжения? С ДРП? Реле мин. давления газа стоит? Что с электропитанием? Когда ТО делали?

    5. Grixak

      Регистрация:
      28.11.13
      Сообщения:


      24

      Благодарности:
      0

      Grixak

      Участник

      Регистрация:
      28.11.13
      Сообщения:
      24
      Благодарности:
      0
      Адрес:
      Москва

      Добрый день!
      Фразировка правильная. Давление в трубе газа низкое без понижающего шкафа и т. д. 12 мба. Дом последний на газовой трубе. Ситуация происходит в разные времена суток.
      Подозреванию временное падение газа в трубе. Реле минимального давления было установленно на 13, установили на 8. Последний раз оикючение произошло в вск с 15 до 20. Причем раньше откючалась одна горелка и котел все же как-то топил, тоиитеперь отключаются обе и сразу.
      ТО не делали, я сам его пылесосил в июне. Проблеммы в работе котла происходят постоянно с момента его установки.

    6. vkramor

      Регистрация:
      29.01.18
      Сообщения:


      413

      Благодарности:
      70

      vkramor

      Живу здесь

      Регистрация:
      29.01.18
      Сообщения:
      413
      Благодарности:
      70
      Адрес:
      Tyumen region Ishim

      12 mB не маловато? хотя для этого котла и 10 должно хватать но это в режиме работы котла а не в статике.

    7. игорь-химик

      Регистрация:
      07.11.14
      Сообщения:


      843

      Благодарности:
      383

      игорь-химик

      Живу здесь

      Регистрация:
      07.11.14
      Сообщения:
      843
      Благодарности:
      383
      Адрес:
      Московская область поселок Гжель

      Я бы этим нехорошим людям из Мособлгаза попробовал бы мозг повыносить, чтобы замерили давление на входе газа когда котел в работе (горелка горит). Блин сволочи, знали какой мощности будет установлен котёл и всё равно выдали ТУ на газификацию, так пусть хоть давление поднимут на ГРП до 300 мм. вод. ст. ГРПшникам это не составит большого труда. :mad:

    8. Mijjgan

      Регистрация:
      10.04.12
      Сообщения:


      22.974

      Благодарности:
      18.015

      Mijjgan

      Супер-Модератор

      Регистрация:
      10.04.12
      Сообщения:
      22.974
      Благодарности:
      18.015
      Адрес:
      Россия, Москва

      Откуда уверенность, что знали? Разве топикстартер что-то говорил о «происхождении» котла? А тот факт, что с момента установки прошло несколько лет и котёл всё это время вываливается в аварию намекает на то, что ни ПНР официально не проводились (минимум — год гарантии), ни договора на ТО нету. Иначе те или другие, забодавшись ездить, уже нашли бы корень зла.

    9. Grixak

      Регистрация:
      28.11.13
      Сообщения:


      24

      Благодарности:
      0

      Grixak

      Участник

      Регистрация:
      28.11.13
      Сообщения:
      24
      Благодарности:
      0
      Адрес:
      Москва

      Волнует больше вопрос автоматического перезапуска котла, может кто сталкивался?

    10. Buderus71

      Регистрация:
      16.01.13
      Сообщения:


      4.897

      Благодарности:
      3.165

      Buderus71

      Живу здесь

      Регистрация:
      16.01.13
      Сообщения:
      4.897
      Благодарности:
      3.165
      Адрес:
      Тула

      @Grixak, Реле давления стоит, значит при нормализации давления газа котёл сам перезапустится. Не было бы — или горелка бы прогорела, или уходил в ошибку и тогда только ручной перезапуск

    11. Roaroma

      Регистрация:
      29.06.13
      Сообщения:


      39.865

      Благодарности:
      17.057

      Roaroma

      чем могу

      Регистрация:
      29.06.13
      Сообщения:
      39.865
      Благодарности:
      17.057
      Адрес:
      Калуга

      @Buderus71, Вы хотите сказать — котел самостоятельно сбрасывает ошибки ?

    12. Buderus71

      Регистрация:
      16.01.13
      Сообщения:


      4.897

      Благодарности:
      3.165

      Buderus71

      Живу здесь

      Регистрация:
      16.01.13
      Сообщения:
      4.897
      Благодарности:
      3.165
      Адрес:
      Тула

      @Roaroma, я хочу сказать что при наличии реле давления газа он в ошибку не уходит.

    13. senns

      Регистрация:
      02.09.15
      Сообщения:


      3.840

      Благодарности:
      1.519

      senns

      Живу здесь

      Регистрация:
      02.09.15
      Сообщения:
      3.840
      Благодарности:
      1.519
      Адрес:
      Екатеринбург

      Судя по ответу автора, там сплошной колхоз делается, т. е. не квалифицированная диагностика.
      К тому же, грит, что одна горелка иногда работает, а это как раз нехватка давления и не факт, что хозяин выставил правильно реле давления газа.
      Пусть ищет спецов

    14. Roaroma

      Регистрация:
      29.06.13
      Сообщения:


      39.865

      Благодарности:
      17.057

      Roaroma

      чем могу

      Регистрация:
      29.06.13
      Сообщения:
      39.865
      Благодарности:
      17.057
      Адрес:
      Калуга

      вот это странно, можете подробнее «разжевать» ?
      если нет газа или давление слабое — котел не разжигает горелку но и не показывает ошибку — я правильно понял ?
      ждет появления необходимого давления и сам запускается при его появлении ?

    15. senns

      Регистрация:
      02.09.15
      Сообщения:


      3.840

      Благодарности:
      1.519

      senns

      Живу здесь

      Регистрация:
      02.09.15
      Сообщения:
      3.840
      Благодарности:
      1.519
      Адрес:
      Екатеринбург

      Реле давления газа отключает напряжение питания котла раньше, чем понизиться давление газа на входе до критического, тем самым котёл «не успевает отобразить» ощибку по газу

    Страница 1 из 3

    Описание товара

    Топочный автомат Satronic / Honeywell DKG 972-N Mod.21 артикул 0432021 применяется в составе атмосферных котлов. Функция менеджера горения – контроль и управление двухступенчатыми горелками. Комплектация не включает цоколь. Аппарат успешно протестирован и сертифицирован по европейским нормам.

    Важные параметры:

    • Предохранительное время: 10 секунд.
    • Время перед розжигом: 3 сек.
    • Режим функционирования: прерывистый.
    • Источник электропитания: 220/240 В, 50/60 Гц.

    Особенности:

    Управляет программным обеспечением встроенный микропроцессор. Автомат обеспечивает высокую стабильность запуска, вне зависимости от бросков в сети, циклов включения, эксплуатационной температуры.

    Программа постоянно отслеживает все стадии работы устройства (включая этап запуска), оповещает о причинах аварийного отключения. Благодаря наличию энергонезависимой памяти данные о причинах автовыключения не утрачивается даже при обесточивании автомата.

    SATRONIC DKG имеет встроенную защиту от низкого напряжения, что обеспечивает высокий уровень безопасности при работе горелки. При достижении минимального уровня напряжения в сети, автомат отключается и препятствует повторному запуску до восстановления рабочих параметров электропитания. Автоматическая защита работает постоянно, а не только при запуске горелки.

    Контроль наличия пламени происходит при помощи ионизационного электрода/ УФ-датчика/ инфракрасного детектора.

    Конструкция

    SATRONIC DKG имеет пластиковый огнестойкий корпус, устанавливаемый с щелчком. Для монтажа прибора на цоколь предусмотрен центральный винт. Цоколь не входит в базовый комплект.

    Электрозащита корпуса отвечает стандарту IP40. Внутри размещен датчик пламени, микропроцессор, электросхемы сброса.  

    На корпусе находится кнопка ручной блокировки/ перезапуска со световой индикацией.

    Достоинства:

    • надежное функционирование горелки;
    • самодиагностика неполадок;
    • оповещение о причинах выключения;
    • действенная защита от низкого напряжения;
    • энергонезависимая память;
    • кожух из огнестойкого материала.

    На нашем сайте можно купить топочный автомат Satronic / Honeywell DKG 972-N Mod.21 по приемлемой цене, оформив заказ через виртуальную корзину. Полную информацию об устройстве уточняйте у сотрудника «АНКАС».

    1. nafsinai

      Регистрация:
      17.03.19
      Сообщения:


      3

      Благодарности:
      0

      nafsinai

      Новичок

      Регистрация:
      17.03.19
      Сообщения:
      3
      Благодарности:
      0

      Buderus Logano G234X (WS) + Logamatic 2109, сгорел Автомат горения DKG 972-N Mod. 21

      Уважаемы специалисты не могли бы Вы дать совет, суть вопроса в чем, год назад установил в частные дом газовый котел Buderus Logano G234X (WS) -60kw с системой управления Logamatic 2109 работало все без нареканий, не давно начались скачки напряжения, после чего котел перестал работать (к дому подведена только 1 фаза, и стоит стабилизатор напряжения РЕСАНТА спн 13500 вход 90-260B, реле-прерывателей нет) Посмотрев систему управления Logamatic выяснил, что все предохранители в целости и сохранности, покопавшись дальше, увидел следы копати на автомате горения, сгорел варистор, выпаяв его результата не дало, котел не запустился, не найдя подробной схемы автомата горения мои скудные знания на этом иссякли я не стал копаться в нем дальше, и заказал новый автомат горения DKG 972-N Mod. 21. После установки нового автомата горения, котел снова заработал. Но вчера произошло опять скачек напряжения, при том что напряжение полностью отключилось и резко появилось. Я сразу пошел проверить котел и опять такая же ситуация, только еще хуже автомат горения пришлось буквально выдирать из котла, клемы пришлось выкусывать так как посадочные места просто расплавились, а в самом автомате горения помимо варистора оплавилась сама плата да так, что я ее из защитного корпуса вытащить не смог. После пошел и проверил всю технику в доме и она вся была целая. Почему при стабилизаторе сгорает только сам автомат горения а все остальное остается целым в том числи и все предохранители в котле? Не уж то данная система настолько уязвима к перепадам напряжения.

    2. ГеннадийВС

      Регистрация:
      19.11.13
      Сообщения:


      760

      Благодарности:
      163

      ГеннадийВС

      Живу здесь

      Регистрация:
      19.11.13
      Сообщения:
      760
      Благодарности:
      163
      Адрес:
      Минеральные Воды

      Тут врядли кто даст четкий ответ на причину. Стабилизатор, а тем более Ресанта, не защищает приборы от импульсных помех (скачкообразных) и сам тоже не защищен, отработать их тем более не сможет, предохранители не успеют перегореть, не всегда успеет защитить варистор, есть более быстрые приборы, например супрессоры, а лучше установить на дом устройство молниезащиты соответствующей мощности для вашего дома. Должно присутствоать правильное заземление. Ваш первый блок управления, думаю, возможно восстановить ищите в своем регионе спеца.
      А регион — Россия, шифруемся?

    3. nafsinai

      Регистрация:
      17.03.19
      Сообщения:


      3

      Благодарности:
      0

      nafsinai

      Новичок

      Регистрация:
      17.03.19
      Сообщения:
      3
      Благодарности:
      0

      Просто быстро регистрацию проходил, а так со станицы Тамань Краснодарского края. А по поводу спеца наверное в самом Краснодаре искать нужно, так как сам автомата горения ближайшее только с Москвы заказывать пришлось.

      Да просто быстро регистрацию проходил, а так со станицы Тамань. Краснодарского края. А по поводу спеца наверное где то в Краснодаре искать нужно, так как автомата горения ближайший с Москвы заказывать пришлось. Сам котел в Краснодаре покупался в еще в 2014 и гарантия уже не действительна(

    4. ГеннадийВС

      Регистрация:
      19.11.13
      Сообщения:


      760

      Благодарности:
      163

      ГеннадийВС

      Живу здесь

      Регистрация:
      19.11.13
      Сообщения:
      760
      Благодарности:
      163
      Адрес:
      Минеральные Воды

      Есть в ваших краях люди способные восстановить. Знаю в Сочах, читал были и ближе. Клич брось, мож кто отзовется. Я с таким блоком не возился, начинать не хочется. Думаютебе, еще клапан надо проверять.

    5. ГеннадийВС

      Регистрация:
      19.11.13
      Сообщения:


      760

      Благодарности:
      163

      ГеннадийВС

      Живу здесь

      Регистрация:
      19.11.13
      Сообщения:
      760
      Благодарности:
      163
      Адрес:
      Минеральные Воды

      Котлы нужно покупать те которые распространены в вашем регионе, и развита сеть сервиса, во многих местах продают зч, не гнаться за брендом и не слушать продавца во все уши… .

    6. dxpoha

      Регистрация:
      20.09.10
      Сообщения:


      2.848

      Благодарности:
      901

      dxpoha

      Живу здесь

      Регистрация:
      20.09.10
      Сообщения:
      2.848
      Благодарности:
      901
      Адрес:
      Самара

      Стаб поменять. Ставь штиль is 550.

    7. Партизан32

      Регистрация:
      13.11.18
      Сообщения:


      3.867

      Благодарности:
      1.708

      Партизан32

      Живу здесь

      Регистрация:
      13.11.18
      Сообщения:
      3.867
      Благодарности:
      1.708
      Адрес:
      Брянск

      Там у вас конец света и зимой и летом. Хотите жить спокойно, поставьте хотя бы РНПП. Стабилизатор — вещь бесполезная в вашем случае.

      Да и Анапы хватит, если поискать.

    8. BoschClimate

      Регистрация:
      28.03.18
      Сообщения:


      133

      Благодарности:
      250

      BoschClimate

      Живу здесь

      Регистрация:
      28.03.18
      Сообщения:
      133
      Благодарности:
      250
      Адрес:
      141400, г.Химки, Вашутинское шоссе, дом 24

      Добрый день!
      Дело в том, что стабилизатор работает в определенном диапазоне напряжений, а также, в зависимости от модели, имеет время реакции. У одних он меньше, у других больше.
      А варистор — это элемент защиты от превышения напряжения, и он срабатывает при напряжении 275В, т. е. это напряжение находится за пределами рабочих параметров Вашего стабилизатора. К тому же отличается время реакции. Типовое значение времени срабатывания варисторов при воздействии перенапряжения составляет не более 25 наносекунд (нс).
      А согласно инструкции к Вашему стабилизатору, его время реакции 5-7 мсек. Поэтому в данном случае говорить о ненадежности оборудования или его уязвимости нельзя — параметры электросети далеко за пределами допустимого напряжения. И это вопрос к поставщику электроэнергии.
      Для дополнительной защиты оборудования, например, можно установить внешний блок с варисторами, как вариант, Теплоком Альбатрос.

    9. nafsinai

      Регистрация:
      17.03.19
      Сообщения:


      3

      Благодарности:
      0

      nafsinai

      Новичок

      Регистрация:
      17.03.19
      Сообщения:
      3
      Благодарности:
      0

      Я уже не знаю что делать… опять заказал новый автомат горения, поставил РНПП после счетчика (только потом пришлось переделывать, и ставить не посредственно перед самим котлом, так как скачки были за 250 В, а ночью за 260 было и постоянные перебои со светом мешали) поставил новый стабилизатор, поставил дополнительное устройство от скачков напряжения, даже установил громоотвод как и советовали, проработало все нормально 4 дня и опять скачек напряжения и опять выгорает только автомат горения на газовом котле. При этом за минуты 3-4 до случившегося я проверял котел и он был выключен так ка работал РНПП, я на срабатывание выставил 250 В приходило 250-255 В, после пошел обедать. Разогревал себе еду в микроволновке и она на доли секунды остановилась и снова запустилась, я сразу в котельную а там только запах гари и выгоренный автомат горения. Опять обошел всю технику в доме и ни одного признака сгорания и выгорания… я не понимаю по чему сгорает только автомат горения, просто не понимаю…

    10. Dmitribir

      Регистрация:
      06.09.16
      Сообщения:


      2.020

      Благодарности:
      1.044

      Dmitribir

      Живу здесь

      Регистрация:
      06.09.16
      Сообщения:
      2.020
      Благодарности:
      1.044
      Адрес:
      Москва и МО Север, Тверская область, Зубцов.

      Попробуйте найти и поставить топочник TFI 812.2, они устанавливались ранее. Переделок никаких не потребуется, все встает на штатные места.

    11. Партизан32

      Регистрация:
      13.11.18
      Сообщения:


      3.867

      Благодарности:
      1.708

      Партизан32

      Живу здесь

      Регистрация:
      13.11.18
      Сообщения:
      3.867
      Благодарности:
      1.708
      Адрес:
      Брянск

      Уважаемый, вы в своём уме ? Какие 250, если 242 должно отключаться. Не, ну если вы хотите, можете 300 поставить и продолжать тут жаловаться.

      Проблема не к форуму, а к энергоснабжающей организации. Им же и счёт выставить надо, за уничтоженное оборудование.

  • Djvu ошибка access violation at address 00000000 read of address 00000000
  • Djvu small mod ошибка конвертирования
  • Djvu reader ошибка failed to set data for
  • Djvu reader ошибка external exception e06d7363
  • Djvu reader не открывает файл пишет ошибку