Mitsubishi electric код ошибки 6834

[7-8 Error Code Definitions and Solutions: Codes [6000 — 6999] ]

7-8-20

1. Error code definition

MA controller signal reception error (Start bit detection error)

2. Error definition and error detection method

Communication between the MA remote controller and the indoor unit is not done properly.

No proper data has been received for 2 minutes.

3. Cause

1) Contact failure of the remote controller lines of MA remote controller or the indoor unit.

2) All the remote controllers are set to SUB.

3) Failure to meet wiring regulations

Wire length

Wire size

Number of remote controllers

Number of indoor units

4) The remote controller is removed after the installation without turning the power source off.

5) Noise interference on the remote controller transmission lines

6) Faulty circuit that is on the indoor board and performs transmission/ reception of the signal from the remote controller

7) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller

4. Check method and remedy

1) Check for disconnected or loose transmission lines for the indoor units or MA remote controllers.

2) Confirm that the power is supplied to the main power source and the remote controller line.

3) Confirm that MA remote controller’s capacity limit is not exceeded.

4) Check the sub/main setting of the MA remote controllers.One of them must be set to MAIN.

5) Diagnose the remote controller (described in the remote controller installation manual).

[OK]: no problems with the remote controller (check the wiring regulations)

[NG]: Replace the MA remote controller.

[6832, 6833, ERC]: Due to noise interference <Go to 6)>

6) Check the transmission waveform, and check the MA remote controller line for electrical noise. For details, refer to the follow-

ing page(s). [8-4 Checking Transmission Waveform and for Electrical Noise Interference](page 264)

7) When no problems are found with items 1) through 6), replace the indoor unit board or the MA remote controller.

The following status can be confirmed on LED1 and 2 on the indoor unit board.

If LED1 is lit, the main power source of the indoor unit is turned on

If LED2 is lit, the MA remote controller line is being powered.

HWE13080

— 238 —

GB

background image

— 34 —

6754

“Отклонение от нормы линии K – Отклонение от нормы датчика дренажа, срабатывание поплавкового реле уровня”

6755

“Отклонение от нормы линии K – Отклонение дренажного насоса от нормы”

6756

“Отклонение от нормы линии K – Образование льда на змеевике / срабатывание защиты от перегрева”

6757

“Отклонение от нормы линии K – Ошибка системы”

6758

“Отклонение от нормы линии K – Неисправность наружного блока, ошибка обмена данными между внутренним и наружным блоком”

6761

“Отклонение от нормы линии K – Отклонение термистора комнатной температуры от нормы”

6762

“Отклонение от нормы линии K – Отклонение от нормы термистора внутреннего змеевика, отклонение от нормы датчика температуры конденсации”

6763

“Отклонение от нормы линии K – Ошибка передачи/приема”

6764

“Отклонение от нормы линии K – Отклонение датчика дренажа от нормы”

6765

“Отклонение от нормы линии K – Отклонение дренажного насоса от нормы”

6766

“Отклонение от нормы линии K – Образование льда на змеевике / срабатывание защиты от перегрева”

6767

“Отклонение от нормы линии K – Неисправность наружного блока, ошибка обмена данными между внутренним и наружным блоком”

6771

“Отклонение от нормы линии K – Отклонение высокого давления от нормы, отклонение низкого давления от нормы”

6772

“Отклонение от нормы линии K – Функция термостата внутреннего блока, отклонение температуры на выходе от нормы,
срабатывание термостата корпуса, срабатывание максимальной токовой защиты”

6773

“Отклонение от нормы линии K – Срабатывание термостата пластины радиатора”

6774

“Отклонение от нормы линии K – Отклонение термистора наружного блока от нормы”

6775

“Отклонение от нормы линии K – Отклонение датчика давления от нормы, Ошибка обмена данными между внутренним и наружным блоком”

6776

“Отклонение от нормы линии K – Отключение по максимальному току”

6777

“Отклонение от нормы линии K – Ошибка системы”

6778

“Отклонение от нормы линии K – Норма”

6779

“Отклонение от нормы линии K – Избыток хладагента, отклонение напряжения от нормы, отклонение датчика CT от нормы”

6800

“Ошибка связи – Другие ошибки связи”

6801

“Ошибка связи – Ошибка связи V-контроль”

6810

“Ошибка связи – Ошибка связи пульта дистанционного управления блока”

6811

“Ошибка связи – Невозможно восстановить синхронизацию пульта дистанционного управления блока”

6812

“Ошибка связи – Сбой аппаратного обеспечения пульта дистанционного управления блока”

6813

“Ошибка связи – Ошибка определения значения разряда состояния связи пульта дистанционного управления блока”

6820

“Другие ошибки связи”

6821

“Другие ошибки связи – Линия передачи данных занята”

6822

“Другие ошибки связи – Отсутствует подтверждение связи”

6823

“Другие ошибки связи – Отсутствует отклик”

6824

“Другие ошибки связи – Ошибка приема данных”

6830

“Ошибка связи – Ошибка пульта дистанционного управления MA, ошибочное повторное задание адреса”

6831

“Ошибка связи – Отсутствует прием сигналов пульта дистанционного управления MA”

6832

“Ошибка связи – Невозможно восстановить синхронизацию пульта дистанционного управления MA”

6833

“Ошибка связи – Нарушение работы аппаратного обеспечения передачи/приема данных пульта дистанционного управления MA”

6834

“Ошибка связи – Ошибка определения стартового бита при обмене данными с пультом дистанционного управления MA”

6840

“Ошибка связи – Ошибка A-контроль, отсутствует обмен данными управления между внутренним и наружным блоком / ошибка приема данных”

6841

“Ошибка связи – Ошибка восстановления синхронизации обмена данными A-контроль между внутренним и наружным блоком”

6844

“Ошибка обмена данными A-контроль между внутренним и наружным блоком, неправильное подключение проводки
между внутренним и наружным блоком, чрезмерное количество внутренних блоков (более пяти)”

6845

“Ошибка связи – Ошибка обмена данными A-контроль между внутренним и наружным блоком, неправильное
подключение проводки между внутренним и наружным блоком (дистанционная связь, разъединение)”

6846

“Ошибка связи – Превышения максимального времени установления связи A-контроль между внутренним и наружным блоком”

7000

“Отклонение системы от нормы”

7100

“Отклонение системы от нормы – Ошибка общей производительности”

7101

“Отклонение системы от нормы – Код ошибки производительности”

7102

“Отклонение системы от нормы – Превышение максимального допустимого количества подключенных блоков”

7103

“Отклонение системы от нормы – Ошибка задания длины трубопроводов”

7104

“Отклонение системы от нормы – Ошибка задания высоты потолков”

7105

“Отклонение системы от нормы – Задан адрес выше 254”

7106

“Отклонение системы от нормы – Ошибка задания атрибута”

7107

“Отклонение системы от нормы – Ошибка настройки распределителя”

7108

“Отклонение системы от нормы – Ошибка настройки системы охлаждения”

7109

“Отклонение системы от нормы – Ошибка настройки соединения”

7110

“Отклонение системы от нормы – Неустановившийся режим соединения системы охлаждения / неустановившиеся данные соединения”

7111

“Отклонение системы от нормы – Входное/выходное оборудование не подключено / отклонение датчика пульта дистанционного управления от нормы”

7112

“Отклонение системы от нормы – Ошибка задания типа входов/выходов”

7113

“Отклонение системы от нормы – Оборудование не установлено”

Error Расшифровка Русский перевод
P1 Intake sensor error Ошибка датчика на входе
P2 Pipe (TH5) sensor error Ошибка датчика теплообменника ТН5 (по схеме)
P4 Drain sensor error/Float switch connector (CN4F) open Переполнение дренажного поддона, или обрыв поплавкового датчика CN4F
P5 Drain pump error Ошибка дренажной помпы
P6 Freezing/Overheating protection operation Ошибка по обмерзанию или перегреву
P8 Pipe temperature error
P9 Pipe (TH2) sensor error Ошибка по датчику теплообменника ТН2
PA Forced compressor stop(due to water leakage abnormality) Принудительная остановка компрессора (из-за переполнения дренажной системы)
E0, E3 Remote controller transmission error Нет связи с пультом управления
E1, E2 Remote controller control board error Неисправна плата пульта управления
E4, E5 Remote controller signal receiving error
E9 Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) Нет связи между внутренним и внешним блоком (Ошибка на внешнем блоке)
EE Communication error between indoor and outdoor units Отсутствует межблочная связь между внутренним и внешним блоками
U1,Ud Abnormal high pressure (63H worked)/Overheating protection operationс Высокое давление по датчику 63Н, или защита от перегрева
U2 Abnormal high discharging temperature/49C worked/insufficient refrigerant Сработал датчик 49С, очень низкое давление нагнетания, недостаток хладагента
U3, U4 Open/short of outdoor unit thermistors Обрыв, короткое замыкание термодатчика внешнего блока
U5 Abnormal temperature of heat sink Температура конденсатора не соответствует норме
U6 Compressor overcurrent interruption/Abnormal of power module Компрессор принудительно остановлен по токовой перегрузке, неисправен силвой модуль
U7 Abnormality of super heat due to low discharge temperatureAbnormal high discharging temperature/49C worked/insufficient refrigerant Сработал датчик 49С / очень низкое давление нагнетания / недостаток хладагента
U8 Outdoor unit fan protection stop Двигатель вентилятора внешнего блока остановлен
U9, UH Abnormality such as overvoltage or voltage shortage and abnormal synchronous signal to main circuit/Current sensor error Повышенное / пониженное напряжение питания, неисправность токового датчика
UF Compressor overcurrent interruption (When compressor locked) Компрессор остановлен из-за токовой перегрузки, компрессор заклинило
UP Compressor overcurrent interruption Остановка компрессора из-за перегрузки по току
Fb Indoor unit control system error (memory error, etc.) Ошибка платы управления внутреннего блока (EEPROM и т.д.)

Определить ошибку в бытовых сплит системах можно по миганию индикаторов на панели внутреннего блока.

Получить расшифровку всех возможных кодов холодильного оборудования Mitsubishi Electric можно на сайте:

Язык оригинальной документации — английский.

Компания Mitsubishi Electric разработала программу для телефонов с помощью которой можно получить расшифровку кода ошибок.

Today we are please to offer the complete list of Mitsubishi aircon error codes. No matter you want to troubleshoot your own Mitsubishi air conditioner or troubleshooting for clients, this mitsubishi ac troubleshooting guide will help.

Let’s get started with Mitsubishi electric air conditioner error codes first.

Mitsubishi error code 0403 (Serial communication error)

Cause : The fault occurs when there is a communication issue between PCB’s in the outdoor unit. If the model number is YGMA, YHMA, YJMA, YKMA or YLMA then the issue can be between the main board and inverter board or main board and fan board.

Check Procedure :

Check for poor connections and broken wiring between the boards. If the model number is YGMA, YHMA, YJMA, YKMA or YLMA, check the error detail code using the dip-switches section of the app to determine which PCB’s the transmission fault is with. If the detail code is 1, then the issue is between the main board and inverter board.

If the detail code is 5 then the issue is between the main board and fan board. Then check for poor connections between the PCB’s.

Mitsubishi error code 0403

Technical Support Notes:

If there are no loose connections on either PCBs and the voltages are good then the Fan or Inverter PCB is usually at fault. This is not normally a problem with the main PCB.

Correct testing should allow you to identify which of the 2 boards is the cause. The online document link will take you to the document library where Service Handbooks can be viewed.

Mitsubishi error code 0900 (Test run)

Cause : Test operation dipswitch on the Lossnay circuit board has been set ON.

Check Procedure :

Check the position of Dipswitch SW2-1 on the main control board. If test is not required then set the dip switch to OFF.

Mitsubishi error code 1102 (Discharge temperature fault)

Cause : Insufficient cooling of the compressor caused by lack of refrigerant or a restriction in the refrigerant circuit, high ambient running conditions or airflow problems on either indoor or outdoor unit (depending on running mode), over heating of compressor through increased friction (compressor beginning to seize), faulty thermistor reading.

Check Procedure :

Use the testing dip switches in the app and check the system running pressures/temperatures and determine if the system is short of gas or if there is a restriction in the circuit – a restriction may show frosting where refrigerant expands, this could be a blocked strainer, faulty expansion valve operation or perhaps moisture in the system.

Check compressor running current -if higher than expected this could show a compressor issue.

Mitsubishi error code 1301 (Low pressure fault)

Cause : Possible refrigerant leak. Restriction or blockage in refrigerant circuit causing low side pressure to drop. Problem with pressure sensor reading incorrectly.

Check Procedure :

Check the system standing pressure for a complete gas loss.

Use the Testing dip switches in the app and compare system gauge pressure to Low Pressure Sensor reading – If the pressure sensor is faulty it will read 0.0 bar even though there is pressure in the system.

Technical Support Notes :

Using the testing dip switches check the system running pressures/temperatures to determine if the system is short of gas or if there is a restriction/blockage in the circuit.

For refrigerant circuit diagram click the link below and type unit model number into the document library search box

Mitsubishi error code 1302 (High pressure fault)

Cause : High pressure faults are commonly caused by a blocked condenser coil, faulty fan motor, a restriction of airflow on indoor units in heating mode or a blockage/restriction in the pipework.

Check Procedure :

Check outdoor fan operates correctly, ensure no restriction of airflow across indoor/outdoor coils such as clogged filters. Use the testing dip switches in the app to check system running pressures/temperatures – This may help highlight any blockages or restrictions in the refrigerant circuit such as faulty solenoid valves or check valves stuck closed.

Technical Support Notes :

If the you reset the unit and the fault generates straight away (without running) then the high pressure switch or sensor may be at fault. Measure the switch for continuity (normally closed) and use the dip switches to check the pressure sensor reading against your gauge pressure.

Mitsubishi error code 1500 (Refrigerant overcharge)

Cause : Normally caused by excessive refrigerant returning to the outdoor unit which over-cools the compressor. System is either over-charged or there are valves operating incorrectly allowing refrigerant to ‘flood’ back to the compressor.

Check Procedure :

Check correct reading of high pressure sensor and discharge thermistor. Check for excessive refrigerant returning to the outdoor unit through overcharge of gas, incorrect valve operation in the system or issue with linear expansion valve (LEV) control in BC Box or Indoor unit

Technical Support Notes :

An indoor LEV stuck open can be an obvious cause to this issue. Try running the system in full cooling and then checking if there is an indoor unit that performs much better than the others.

Mitsubishi error code 2500 (Drain sensor submergence)

Cause : Water pump off/faulty. Water flow rate too slow. Float switch faulty.

Check Procedure :

Check water pump. Check water flow rate. Check continuity of float switch.

Mitsubishi error code 2500
Drain sensor submergence

Mitsubishi error code 2502 (Drain pump fault)

Cause : The indoor unit drain float has detected a high water level in the drip tray.

Check Procedure :

Check the indoor drip tray for water. If there is excessive water then there may be an issue with the internal pump or drains. If the tray is dry or hasn’t enough water to lift the float switch then check the float switch for continuity. If the switch is lifted the circuit should be made. If the switch is down then the circuit should be open.

Mitsubishi error code 2502

Technical Support Notes :

The internal lift pump is not activated by the float switch, the pump is activated when cooling mode is selected. This fault is triggered by the float switch circuit closing.

Mitsubishi error code 2503 (Drain sensor fault)

Cause : The drain sensor is open/short circuit.

Check Procedure :

If the drip tray is clear then check the resistance of the drain sensor as an open circuit or short circuit can cause the fault.

Mitsubishi error code 2503

Technical Support Notes :

Check the wiring diagram to see if the indoor unit has a float switch or sensor. If the wiring diagram shows a float switch and not a sensor check the dip switch settings for the unit model you are working on.

Mitsubishi error code 2600 (Water leakage)

Cause : Water leak from pipes on humidifier.

Check Procedure :

Check that water does not leak from pipes in humidifier.

Mitsubishi error code 4102 (Open phase)

Cause : Missing main phase.

Check Procedure :

Check power supply and noise filter for correct 3 phase, check wiring and fuses.

Mitsubishi error code 4106 (Transmission power supply fault)

Cause : Transmission (M-Net), incorrect wiring.

Check Procedure : Check wiring, high current, incorrect voltage on transmission line and/or M-Net board. Make sure M-net transmission wiring is daisy chained.

Mitsubishi error code 4115 (Power supply signal sync error)

Cause : Incorrect power supply, blown fuses or possible faulty PCB.

Check Procedure :

Check mains power is correct, check the fuses, and connections PCB.

Mitsubishi error code 4116 (RPM error/Motor error)

Cause Check Procedure
Faulty connection of a fan. Check the connection for the fan motors.
Faulty connection of the leads between the Control board and the Power board. Check the connections between the Control board and the Power board.
Model selection switch SW6 is set incorrectly. Confirm that the model selection switch SW6 is set correctly for the model.
Ambient temperature in which the unit is located is high. Check the temperature around the Lossnay.
Fan isn’t fixed correctly. Confirm that the fan motors are fixed securely.
Deformed centrifugal fan. Check that the centrifugal fan is clear of debris.
Centrifugal fan has foreign objects in or around it. Replace the fan motor.
Fan motor fault. Replace the circuit board.
Circuit board fault. Check the connections of the reactor (TB3-4) and check the resistance of it.
Faulty connection of the reactor. To identify which fan the issue is with, check the LED flashing sequence and contact After Sales Technical Support.
Mitsubishi error code 4116

Mitsubishi error code 4220 (Abnormal bus voltage)

Cause : Low mains power supply, diode fault.

Check Procedure :

Check mains supply. Check DC bus voltage coming from diode.

Mitsubishi error code 4225 (Low bus voltage)

Cause : Incorrect mains supply or fan board fault.

Check Procedure :

Check mains power is ok and there is at least 300vdc at the diode stack.

Mitsubishi error code 4225

Technical Support Notes :

Check to see if the error led is lit on the fan board, this is a good indication that the fan board is the issue.

Mitsubishi error code 4230 (Heatsink overheat protection)

Cause : Blockage in air passage of inverter heatsink, Inverter board failure, inverter fan failure.

Check Procedure :

Check blockages in air duct failure of INV fan or failure of thermistor.

Mitsubishi error code 4240 (Overload protection)

Cause : If high current is detected for more than 10mins.

Check Procedure :

Check inverter balance. Reduced airflow through heat sink.

Mitsubishi error code 4250 (Over current protection)

Cause : High amps drawn by the compressor or an issue with the inverter.

Check Procedure :

Carry out an inverter output test to check if the inverter is working correctly. Use the “inverter testing guide” in the City Multi section of the APP. If the inverter is ok then check the compressor windings for a short or open circuit.

Technical Support Notes :

Use the service dipswitches on the outdoor unit to get the detail code which will indicate if the issue is with the inverter or compressor.

Mitsubishi error code 4255 (Outdoor fan error)

Cause : Grounding fault of fan motor or fan board fault.

Check Procedure :

Check the voltage on CNVDC on the fan. This should be a high DC voltage around 580vdc.

Also check the fan motor windings for an open or short circuit.

Technical Support Notes :

Use the service dipswitches on the outdoor unit to get the detail code which will indicate if the issue is with the fan board or fan motor.

Mitsubishi error code 4260 (Heatsink overheat protection at startup)

Cause : Reduced airflow through heat sink.

Check Procedure :

Fan motor problem. THHS thermistor problem.

Mitsubishi error code 5101 (Temperature sensor fault)

Cause Check Procedure
Faulty thermistor – dead short/open circuit. The fault can be related to indoor or outdoor so check the fault code for address of unit in fault first.
Damaged thermistor cable or poor connection to PCB. Check connection of thermistor on PCB and thermistor wiring.
PCB incorrectly reading thermistor value. Unplug thermistor and test resistance value.

If all the above are correct then replace the PCB.

Technical Support Notes :

Correct reading of thermistor can be determined using Thermistor Value Look Up in the app.

Check whether the thermistor is for reading High temperature e.g .Discharge, or Normal running e.g. Ambient/Liquid, to determine which range to check against.

Mitsubishi error code 5102 (Return Air thermistor fault)

Cause : The circuit board cannot read the thermistor correctly

Check Procedure :

Check the connection onto the circuit board.

Check the resistance of the thermistor.

Replace the thermistor.

Replace the circuit board.

Mitsubishi error code 5110 (Outdoor inverter heatsink thermistor error)

Cause : Reduced airflow through inverter heatsink.

Check Procedure :

Open/short circuit sensor, disconnected from PCB.

Mitsubishi error code 5110

Technical Support Notes :

On the YGM-A series this can be either THHS1 or THHS5. To find out which it is you will need to check the inverter detail code using SW1 on the control board. Turn on SW1 dips 1,2,5,6,8 and look at the display for the code to be retrieved. THHS1=01 and THHS5=05.

Mitsubishi error code 5201 (Pressure sensor fault)

Cause : PS1 Pressure fault.

Check Procedure :

Check pressure reading using the dipswitches on the outdoor. Check connection of PS3 on PCB.

Mitsubishi error code 5301 (Current sensor fault)

Cause : ACCT or DCCT sensor error.

Check Procedure :

Check inverter error details, check resistance of current sensor, check connections of sensors.

Mitsubishi error code 5701 (Loose float switch connector)

Cause : The indoor unit internal float switch connector has detected an open circuit.

Check Procedure :

Check the float switch is operating correctly. If the switch is down then the switch should be open.

Also check for external pumps wired in across the fail safe connection.

Mitsubishi error code 5701

Technical Support Notes :

This fault normally occurs when an external pump is wired in across the fail safe connections, (CN4F/CN31) and the external pump has failed. Or the connection is loose.

Mitsubishi error code 6201 (Remote controller issue)

Cause : The remote controller is faulty

Check Procedure :

Replace the controller.

Mitsubishi error code 6600 (Address overlap)

Cause : There is more than one unit with the same MNET address or two or more devices are addressed the same.

Check Procedure :

Check the address set on each device on the same MNET network.

Check address settings on outdoors, indoors, BC boxes and remote controllers to see if two have the same address settings.

Mitsubishi error code 6600

Technical Support Notes :

This is only caused when two items are addressed the same. If they all look like they are set correctly power the system down and spin the address dials all the way around to confirm they are clicked into the position they should be. If the system also has a 6607 fault this could indicate where the repeat address has occurred.

Mitsubishi error code 6601 (Polarity setting error)

Cause : No voltage or short circuit on M-Net transmission line TB7.

Check Procedure :

Check TB7 connections on outdoors and central controllers. Check for voltage on TB7. Check cable size and spec.

Mitsubishi error code 6602 (Transmission processor hardware error)

Cause Check Procedure
Noise interference. Polarity problem on TB7. Check M-Net connection on TB7 and central controller. Check cable size/spec.
Controller where the error originally occurred is defective. Check the controller where the error occurred and replace if required.
Lossnay circuit board is defective. Replace the circuit board.
Mitsubishi error code 6602

Mitsubishi error code 6603 (Transmission line bus busy error)

Cause :

Power is supplied to the same transmission cable from two or more power supply units.

The power supply unit is connected to TB3 side of the power supply expansion units.

The power supply units connected to the indoor and outdoor transmission cables.

Check Procedure :

Adjust the wiring of the power supply unit.

Mitsubishi error code 6603

Mitsubishi error code 6606 (Communication fault)

Cause :

Poor connection of MNET terminals.

MNET cables have been terminated whilst the unit is powered.

Malfunction of the unit PCB.

Check Procedure :

Check that the MNET cables have been terminated correctly.

Reset power to the system.

Inspect the Control Board for damage.

Replace the Control Board.

Mitsubishi error code 6606

Mitsubishi error code 6607 (No ACK error)

Cause :

Lossnay has no power.

Lossnay address has been changed.

Transmission cable is in excess of 500m.

Transmission cable is not securely terminated.

Check Procedure :

Check the power supply to the Lossnay.

Check the Lossnay address.

Check the cable length.

Check the cable termination.

Technical Support Notes :

The 6607 fault should also give you the address of the item in fault, if it does check power and M-Net voltage at the item.

If no address is given with the fault code then this is referred to as a “ghost fault”, this is caused when something with an address is physically removed from the system without being deleted first.

Mitsubishi error code 6608 (No response error)

Cause :

When using multiple Lossnay units, the Main/Sub switch has not been set.

Interference on the transmission line.

Cable length is in excess of 500m.

Transmission cable is not securely connected.

Multi core cable is being used for multiple uses and causing interference.

Check Procedure :

Isolate power and set the lead unit to Main using SW1 and the remaining units to Sub.

Check and repair cable terminations.

Check the length of the transmission cable.

Check that the cable used is as specified.

Mitsubishi error code 6608

Mitsubishi error code 6831 (MA controller signal reception error)

Cause : MA controller being wired into the M-Net. Wrong cable size/spec.

Check Procedure :

Check where remote is wired to, check cable length no bigger than 500 meters, check connection and type of cable used, check R/C not set Sub on field settings.

Mitsubishi error code 6831

Mitsubishi error code 6832 (MA controller comms fault)

Cause : MA controller being wired into the M-Net. Wrong cable size/spec.

Check Procedure : Check where remote is wired to, check cable length no bigger than 500 meters, check connection and type of cable used, check R/C not set Sub on field settings.

Mitsubishi error code 6832

Mitsubishi error code 6833 (MA controller comms fault)

Cause : MA controller being wired into the M-Net. Wrong cable size/spec.

Check Procedure :

Check where remote is wired to, check cable length no bigger than 500 meters, check connection and type of cable used, check R/C not set Sub on field settings.

Mitsubishi error code 6833

Mitsubishi error code 6834 (MA controller signal reception error)

Cause : MA controller being wired into the M-Net instead of the remote terminals. Wrong cable size/spec.

Check Procedure :

Check where remote is wired to, check the cable length is no bigger than 500 meters, check connection and type of cable being used, check R/C not set Sub on field settings.

Mitsubishi error code 6834

Technical Support Notes :

This is usually caused when an M-Net controller is replaced with an MA controller. Make sure if you have an M-Net remote it is wired into the M-Net terminals and if you have an MA remote it is wired into the remote controller terminals.

Mitsubishi error code 7100 (Total capacity error)

Cause :

The total indoor unit capacity exceeds the outdoor unit allowable capacity.

On a PURY outdoor you are allowed up to 150% of its capacity.

On a PUHY/PUMY outdoor you can have up to 130% of its capacity.

Check Procedure :

Add up all the capacities of the indoor units and check they don’t exceed the outdoor unit capacity.

Also check the capacity dip switches on the indoor and outdoor unit are set correctly.

Technical Support Notes :

This fault can be caused when the system is comprised of two outdoor units piped together and power is lost to one of the outdoors.

Mitsubishi error code 7101 (Capacity code setting error)

Cause : SW2 set wrong on indoors, SW5 dips set wrong on YHM-A outdoor, SW3-10 on older kit.

Check Procedure :

Capacity dips on indoor and outdoor units.

Mitsubishi error code 7101

Mitsubishi error code 7102 (Wrong number of connected units)

Cause : The outdoor unit is not seeing any indoor units or it is seeing more than the allowable value.

Check Procedure :

Check voltage on M-Net, power to the BC box, check dip switches are set correctly on the BC box and the model type of BC box is correct for the system.

Technical Support Notes :

Check the voltage on the M-Net at the outdoor unit (it should be 29vdc). If there is no voltage then power down and remove the M-Net and check the terminals again. If you then get 29vdc then there is an issue somewhere on the M-Net, a loose connection or short maybe.

Mitsubishi error code 7105 (Address setting error)

Cause : OC or BC addressed wrong.

Check Procedure :

Check address setting on OC and BC.

Mitsubishi error code 7106 (Attribute setting error)

Cause : GUF unit being used on City Multi system.

Check Procedure :

Make sure SW3-1 setting is on, on the GUF.

Mitsubishi error code 7110 (Signal transmission error)

Cause : Loose or misswiring of TB3 or TB7. SW5 dip 7 not set on outdoor. Transmission booster turned off.

Check Procedure :

Check M-Net connections, dipswitches on outdoors.

Mitsubishi error code 7111 (Remote controller sensor fault)

Cause : SW1 – 1 on and no controllers fitted or faulty remote controller.

Check Procedure :

Check SW1 – 1 on the indoor unit if no remote controllers fitted.

Mitsubishi error code 7111

Mitsubishi error code 7113 (Function setting error)

Cause :

More than 1 unit in the group is set to as the Main Lossnay (SW5-10 ON)

The group contains two or more units with the same address.

The Lossnay that is set to the Main, has not been set to the lowest unit address in the group.

The MA remote controller for the air conditioner (Mr.Slim or City Multi) is connected to the Lossnay.

Incorrect wiring of the remote controller terminals.

The Lossnay LGH-RVX is in the same group as a Lossnay LGH-RX5.

The model selection switch SW6 is not set correctly.

Check Procedure :

Check the SW5-10 setting on the Lossnays in the same group and confirm that there is only one set to Main(ON)

Check the address settings of the Lossnay units.

Change the remote for a PZ-61DR-E.

Check that the wiring of the remote terminals and the MNET terminals.

The LGH-RVX and the LGH-RX5 cannot be used in the same group.

Confirm that the SW6 setting is correct for the model.

Mitsubishi error code 7117 (Model setting error)

Cause : SW5 set wrong on the outdoor or wrong resistors fitted.

Check Procedure :

Check dips, resistors and thermistors.

Mitsubishi error code 7130 (Incompatible unit combination)

Cause : Check split with MAC 399 wired onto the TB5 line not the TB7.

Check Procedure :

Check M-Net wiring on systems.

Now, let’s proceed with Mitsubishi heavy air conditioner error codes. If you want to learn more about Mitsubishi heavy vs electric, please refer to our previous guide for more info.

Mitsubishi error code E1 (Remote controller communication issue)

Cause : Faulty controller or poor wiring connection/abnormal voltage to the Remote controller

Check Procedure :

Check the remote controller wiring connection onto the FTC terminals and ensure there is 12vdc down to the Remote controller.

Make sure LED2 is lit on the FTC Control board

Mitsubishi error code E2 (Remote controller transmitting error)

Cause : Incorrect wiring of remote or incorrect dip switch setting if units are grouped.

Check Procedure :

Check unit addressing if grouped or check remote is only wired to master indoor unit.

Mitsubishi error code E3 (Remote controller communication/receiving error)

Cause :

Incorrect settings on SW1 switches at the outdoor unit.

Poor connection or wiring of the remote controller.

Check Procedure :

Check for 12vdc down to the controller and make sure LED 2 is lit on the FTC board

Check the SW1 dips switches on the outdoor unit are set correctly.

Mitsubishi error code E5 (Remote controller communication/receiving error)

Cause :

Remote controller incorrectly wired or the controller does not have the correct 12vdc supply.

Incorrect settings on SW1 switches at the outdoor unit.

Check Procedure :

Check for 12vdc down to the controller and make sure LED 2 is lit on the FTC board.

Check the SW1 dips switches on the outdoor unit are set correctly.

Mitsubishi error code E6 (Indoor to outdoor communication fault)

Cause : Loss or no communication between the FTC and outdoor Ecodan. Poor connection of the interconnecting cable or not the correct 12-24vdc fluctuating voltage between S2 and S3.

Check Procedure :

Reset power supply to both indoor FTC and outdoor Ecodan. Power back up the indoor first then the outdoor. Check interconnecting cable connections and voltages. Check indoor FTC LEDs.

Technical Support Notes :

The most common cause of an E6 fault is external noise interference caused by condensate pumps being wired into S1 & S2. If a pump is wired in to S1 & S2 and you have an E6, then try disconnecting the pump and repowering the system to see if it works.

Mitsubishi error code E7 (Comms failure indoor to outdoor)

Cause : Mis-wiring of indoor to outdoor cable. System powered up incorrectly.

Check Procedure :

Check for pumps wired in, Check indoor isolator, Repower in correct sequence i.e. indoor then outdoor.

Mitsubishi error code E8 (Indoor to Outdoor communication error)

Cause : Loss or no communication between the FTC and outdoor Ecodan. Poor connection of the interconnecting cable or not the correct 12-24vdc fluctuating voltage between S2 and S3.

Check Procedure :

Reset power supply to both indoor FTC and outdoor Ecodan. Power back up the indoor first then the outdoor. Check interconnecting cable connections and voltages. Check indoor FTC LEDs.

Mitsubishi error code E9 (Indoor to outdoor communication error)

Cause :

Loss or no communication between the FTC and outdoor Ecodan. Poor connection of the interconnecting cable or not the correct 12-24vdc fluctuating voltage between S2 and S3.

SW8-3 set to OFF when independent power supplies are used.

Check Procedure :

Reset power supply to both indoor FTC and outdoor Ecodan. Power back up the indoor first then the outdoor. Check interconnecting cable connections and voltages. Check indoor FTC LEDs.

Power down complete system and set SW8-3 to ON before powering the FTC before the Ecodan.

Кондиционеры Mitsubishi-Electric, ошибки R410A

Определение ошибки при помощи светодиода Mitsubishi-Electric

Таблица неисправности сплит систем Mitsubishi-Electric

  • Серия Делюкс (инвертор)
    MSZ-FA25/35VA
    MUZ-FA25/35VA
  • Серия Mitsubishi-Electric, ошибки… стандарт (инвертор) R410A
    MFZ-GA25/35/50VA
    MUZ-GA25/35/50VA
  • Серия Mitsubishi-Electric стандарт (без инвертора, конденсаторный пуск) R410A
    MSC-GA20/25/35VB
    MSH-GA50/60/80VB
    MUH-GA20/25/35/50/60/80VB

Только охлаждение
MSC-GA20/25/35VB
MS-GA50/60/80VB
MU-GA20/25/35/50/60/80VB

  • Серия стандарт (без инвертора) R22
    MSC-A07/09/12YV
    MSH-18/24/30RV
    MUH-07/09/12/18/24/30RV

Только охлаждение
MSC-A07/09/12YV
MS-18/24/30RV
MU-07/09/12/18/24/30RV

Коды неисправностей.

Дисплей на пульте дистанционного управления, нажать и удерживать кнопки пульта дистанционного управления, ПРОВЕРИТЬ и SET в течение 4 секунд

Mitsubishi-Electric. Slim А-контроль

Код EA
Неправильный монтаж внутреннего / наружного блока. Проверить межблочное соединение, электрическая цепь. Обрыв цепи.

Код Eb
Неправильный монтаж, отключения, сработала защита.

Код ЕС
Ошибка запуск по времени, в течение 5 мин. Выключить питание, обесточить сплит систему Mitsubishi-Electric, вынуть батарейки из дистанционного пульта управления. Далее проделать операцию через 5 мин. в обратном порядки.
Все настройки сплит системы вернутся к заводским по- умолчанию.

Неправильный монтаж внутреннего / наружного блоков как правило ведёт к поломкам сплит системы..

Mitsubishi-Electric инверторного типа, таблица неисправностей.

Обрыв связи.

Код E6

  • Ошибка соединений внутреннего / наружного блока, датчик приёма сигнала (нет приема сигнала).

Сигнала нет, замыкание.

Код E7
Ошибка внутреннего / наружного ошибка блока передачи (ошибка передачи).
Сигнала нет, замыкание.

Код E8
Ошибка, не работает датчик приёма, проверить приходит ли питание к датчику.
Обрыв цепи.

Код E9
Ошибка внутреннего / наружного ошибка межблочного соединения.
Обрыв цепи. Сигнала нет.

Код E0 Нет сигнала от пульта управления (прием сигнала)
Поменяйте батарейки пульта ду.

Код E3

  • Не правильный сигнал. ПУ кондиционера не правильно формирует сигнал.
    Исправить, — См. Код ЕС

Код Е4

  • Проверить межблочное соединение, целостность датчиков температуры и давления.

Код E5

  • Проверить напряжение в сети. Возможны сбои в работе оборудования.

Код EF
Ошибка M-NET, — нет сигнала

  • Проверить межблочное соединение, обрыв соединений или плохой контакт.

Код Эд
Последовательность формирования сигнала нарушена. Сбой шагового- искателя.
Исправление, — см. Код ЕС Mitsubishi-Electric, — вернуться к заводским настройкам кондиционера по умолчанию.

Код P1
Не работает датчик температуры  (Th3).

  • Проверить датчик на целостность. Нарушена герметичность датчика, датчик и соединительный кабель настолько грязные и мокрые, что замыкают. При необходимости заменить датчик

Код P2

Датчик обморожения внутреннего блока, сработал датчик.
Грязный внутренний блок, плохое прохождение воздуха, вследствии обморожения. Проверить контур сплит системы Mitsubishi-Electric на утечку газа.
Обморожение как правило начинается из-за недостатка газа или кондиционер требует к себе внимания, — профилактики.

Код P4
Проверить дренаж, слив, — сработал датчик переполнения ванны. Забит слив.

Код P5
Не работает сток, двигатель дренажа работает в холостую.

Ремонтируем сплит системы, кондиционеры Mitsubishi-Electric до 2006 года выпуска

Коды ошибок. Mitsubishi-Electric до 2006 года выпуска

Код P6
Ошибка, —

  • Замораживание / сработала защита от перегрева. Проверить контур сплит системы на утечку газа.

Обморожение как правило начинается из-за недостатка газа.

Код P8
Температурный режим вышел за заданные параметры, проверить датчик температуры на целостность. Сопротивление датчика должно быть в пределах 16 Ом.

Код P9
Датчик температуры замкнут.

  • Проверить датчик на целостность. Нарушена герметичность датчика, датчик и соединительный кабель настолько грязные и мокрые, что замыкают(TH5)

Замыкание.

Код F1

  • Проверить фазировку на двигателе компрессора наружнего блока кондиционера   Mitsubishi-Electric.

Код F2
Ошибка L3 обрыв фазы.

Код F3
Ошибка 63L нет сигнала с платы управления.

  • проверить качество формирования сигнала, проверить датчики на целостность, возможная причина, 0 — подгорели контакты реле включения, залипания контактов, неисправность пружины реле…

Код F4
Ошибка 49C разъем разомкнут.

Код F9
Ошибка, — разъем 2 или более нет сигнала.

Код FA
Ошибка L2- обрыв фазы или 51см разъем разомкнут.

Код F7
Ошибка последовательности фаз шлейфа, проверить состояние кабеля.

Код F8
Сбои в питании, проверить напряжение в сети.

Код U2
Высокие температурные параметры работы компрессора, сработала защита от перегрузки.

Код U2
Ошибка

  • Внутренний термостат (49C) проверить причины сработки, проверить рабочие и пусковые токи компрессора кондиционера, напряжение питания, количество и давление газа фреона в холодильном контуре сплит системы.

Код U1
Датчик давления (высокое давление swicth 63H сработал)

Код U1
Фатальная ошибка.

Код УП
Ошибка

    Высокое давление в системе, шаровой кран закрыт, залом меж.блочной трассы, не работает перепускной клапан, задир, залип…Постучать тук-тук-тук.

Код UL
Низкое давление в системе, сработал датчик.

Код Ud
Сработала тепловая защита компрессора кондиционера. Смотреть исправление и причины, — код U2

Код U6
Перегрузка компрессора. Смотреть исправление ошибки и причины, — код U2

Код UA
Ошибка компрессора. Проверить пусковое реле.

Код UF
Нет сигнала блокировка пуска. Фатальная ошибка, неисправно всё, начинай проверку сначала.

Например смотреть неисправности тык

а) неисправности электрической части, системы эл. питания и управления кондиционером. рис. 1.

б) неисправности холодильного контура, рис. 2.

Блокировка пуска компрессора, неверные входящие и разрешающие пуск параметры.

Код UH
Текущая ошибка датчика.

Код U3
Проверить конденсатор, недостаточное сглаживание по току, варистор неисправен.

Код U4
Не работает датчик температуры наружнего блока кондиционера.

Коды P1-P8 | Mitsubishi-Electric .Slim K-контроль

Дисплей на пульте дистанционного управления Mitsubishi-Electric.

Горит лампочка светодиода E0
Диагностика неисправности приема / передачи сигнала ошибки.
Сигнала нет, замыкание датчика.

Горит лампочка светодиода P1
Диагностика неисправности датчиков всасываемого воздуха, ошибка.
Сигнала нет, замыкание.

Горит лампочка светодиода P2
Диагностика неисправности труб, датчик T- ненормальный.
Сигнала от датчика нет, замыкание.

Горит лампочка светодиода P4
Датчика Drain ненормальный, выбросить в мусорное ведро.

Горит лампочка светодиода P5
Неисправное соединение, — утечка переполнения защиты механизма.
Сигнала нет, замыкание.

Горит лампочка светодиода P6
Диагностика неисправности Abnomality датчик обморожения / защита от перегрева режиме.
Сигнала нет, замыкание.

Горит лампочка светодиода P3
Диагностика неисправности системной ошибки (передача / прием сигнала)
Сигнала нет, замыкание.

Горит лампочка светодиода P7
Диагностика неисправностей Системная ошибка (адрес)
Сигнала нет, замыкание.

Горит лампочка светодиода P8
Диагностика неисправности Открытый неисправности блок
Обрыв цепи.

Подробнее: Ошибки P1, P2, P3, P4, P5, P6

Mitsubishi-Electric. — Mr.Slim K-контроль PUH-EK

Наружный блок

LED ON статус операции =
Светодиодная вспышка = Проверка кода diplay

Горит лампочка светодиода LD1
LED ON Компрессор директивы
Светодиодная вспышка последовательности фаз обнаружить

Горит лампочка светодиода   LD2
LED ON Отопление директивы
Светодиодная вспышка Открытая фаза обнаружения

Горит лампочка светодиода LD3
LED ON Во время операции 63h3
Светодиодная вспышка трубы датчика короткий / открытые

Горит лампочка светодиода LD4
LED ON компрессора
Светодиодная вспышка высокого давления swicth (63H2) операции.

Горит лампочка светодиода lD5
LED ON Открытый вентилятор включаются
Светодиодная вспышка от перегрузки по току реле (51 см) операции.

Горит лампочка светодиода LD6
LED ON 4-ходовой клапан ON
Светодиодная вспышка тепловых swicth- светодиодов (26C) операции.

Горит лампочка светодиода LD7
LED ON Перепускной клапан Mitsubishi-Electric ON
Светодиодная вспышка Термистор (TH3) защита от перегрева.

Горит лампочка светодиода LD8
LED ON Нагреватель картера ON
Светодиодная вспышка Mitsubishi-Electric, — пассивный ввод.

Mitsubishi-Electric: неисправности в работе сплит-систем, коды ошибок

Mitsubishi Electric | Неисправности сплит систем, коды ошибок. Эти коды ошибок даны для следущих моделей сплит систем.

Серия Mitsubishi-Electric Делюкс (инвертор)
MSZ/MUZ-FA25/35VA

Серия Mitsubishi-Electric стандарт (инвертор) R410A
MFZ/MUZ-GA25/35/50VA

Серия Mitsubishi-Electric стандарт (без инвертора, конденсаторный пуск) R410A
MSC/MUH-GA20/25/35/50/60/80VB

Только охлаждение
MSC-MU-GA20/25/35/50/60/80VB

Серия Mitsubishi-Electric стандарт (без инвертора) R22
MSC-MSH-MUH-07/09/12/18/24/30RV

Только охлаждение
MSC-MU-07/09/12/18/24/30RV

Начинать проверку сплит системы на работоспособность необходимо, с замеров напряжения в сети и замеров токовых характеристик наружного блока кондиционера.

Важно:  Перед установкой сплит системы обратите внимание на целостность упаковки. Замечены случаи несанкционированного доступа к платам внутренних блоков, неквалифицированный монтаж кондиционеров данного вида кондиционеров ведёт к выходу платы внутреннего блока к поломке.

Монтажники путают провода межблочного подключения в следствии чего плата перегорает. Не долго думая они, эти горе специалисты меняют на складе плату на новую (с другой сплит системы Mitsubishi-Electric) тщательно маскируя подмену.Кондиционеры Mitsubishi-Electric | Неисправности сплит-систем, коды ошибок

Не нарвитесь на неликвид. Перед установкой тщательно проверяйте как упаковку, так и следы вскрытия. При малейших подозрениях такую сплит систему не устанавливайте. Высокая вероятность подмены  платы внутреннего блока на неисправную. Левый индикатор моргает постоянно…

Ремонтируем сплит системы, кондиционеры Mitsubishi-Electric до 2006 года выпуска

Коды ошибок. Mitsubishi

  • Mitsubishi colt ошибка p1970
  • Mitsubishi colt ошибка eps
  • Mitsubishi colt ошибка b1401
  • Mitsubishi carisma ошибка srs
  • Mitsubishi carisma ошибка p0170