If you are looking for a solution to fix the Error Code HCNetSDK.dll[91] on your Hikvision camera, don’t look any further. Just read this article…

Hikvision Reconnecting Error Code 91

There are two main reasons to have this issue with your IP camera.

The Hikvision reconnecting Error Code HCNetSDK.dll[91] occurs when there’s no enough power for the camera or when the Auto Change stream type is on. The easiest solution to solve the problem is to use a better PoE power supply and turn the auto change stream off.  

The problem with power

When using PoE (Power Over Ethernet) to power the camera up, is necessary to follow the international standards such as the IEEE 802.3af and IEEE 802.3at to have enough power.

IP camera using PoE

Each one these IEEE standards are designed to have specific voltage (V) and power (W) for the cameras and you need to use the correct power supply to have your camera working properly without some type of error. 

You can use either a PoE switch or a PoE power supply, just ask the vendor a model that follows the IEEE 802.3af standard for fix cameras (dome or bullet) or the IEEE 802.3at standard for PTZ cameras.

Some users and technicians have reported a problem with the message in the iVMS-4200 screen «Reconnecting.Error Code HCNetSDK.dll[91]» due to the lack of power for the camera (when using the wrong PoE power supply).

Just make sure you are using the correct PoE power supply or switch.

To learn more about PoE read the article PoE switch for IP camera

The auto change stream type 

The IP camera or recorder generates a different type of video stream such as main stream and sub stream to send through the network.

Those type of stream can vary according to the resolution, frame rate and compression (such as H.264, H.264+ and H.265) and when the camera changes the stream automatically that can cause some issues.

To prevent the Reconnecting.Error Code HCNetSDK.dll[91] error just open the iVMS-4200 to change the parameter (see the picture below).

Click Tools —> System Configuration

iVMS-4200 System configuration

Just uncheck the Auto-change Stream Type option in the Image Menu

Change the auto stream parameter

This simple change should do the job, now just come back to the main screen and reload the cameras and the error should go away.

Hikvision camera without the error

If some reason the cameras are still not loading properly just restart the iVMS-4500, sometimes a refresh can save the day.

Other factors to consider

If you follow the instruction above everything should work correctly, however, sometimes there are some details that can prevent your camera to work.

Let’s see some extra procedures to help you get rid of the problem.

Infrastructure (cables)

Remember we talked about the use of the correct PoE switch or Power supply to power the camera up? 

Guess what… they send power through cables ! 

If you are not using good quality cables the power or data can be compromised and your system can fail and sometimes even generate the same «Reconnecting.Error Code HCNetSDK.dll[91]»  error.

For IP camera is recommended to use cat5e or cat 6 UTP cables.

UTP cable

Also, make sure the cable are from a good manufacturer such as Furukawa or another brand that is reliable.

You also have to take the distance into consideration, the limitation for UTP cable for data transmission is 100m according to the international standard.

Camera factory default reset

Sometimes a bad configuration or a corrupted configuration file can hold your camera in an error state, so it’s a good practice to reset the device to factory default and reconfigure it from scratch.

Just login into the camera, go to the Upgrade & Maintenance menu.

Click the restore button (see the picture below).

Hikvision DVR factory default

After restoring the camera to factory default configure it manually (don’t import a file with the old configuration).

Firmware upgrade

It’s important to keep all the devices with the last firmware to make sure everything works fine, so take a look at the manufacturer website to see if there’s a new firmware for your device.

You can also go directly to your device menu and click the button to check for the last firmware available.

Hikvision DVR check for new firmware

Conclusion

The Reconnecting.Error Code HCNetSDK.dll[91]» can be eliminated by following the instructions in this article, just make sure to execute each step and if some reason the problem still remains call the Hikvision support.

I hope this article can help you to solve your problem.

Want to learn more ? 

If you want to become a professional CCTV installer or designer, take a look at the material available in the blog. Just click the links below:

Ultimate Guide V3

Please share this information with your friends…

The Hikvision Reconnecting.Error Code HCNetSDK.dll[91] occurs on the iVMS-4200 software and it’s an indication that there’s not enough power juice for the camera or that the Auto-change stream type is enabled.

The fastest solution to solve this issue is to use a better PoE switch and turn the auto-change stream type off. In this guide, you can find steps on how to fix this reconnecting error code issue.
Hikvision Error Code 91

1. Not enough power

This is most likely the main cause of this issue. The camera is not getting enough power juice, it’s struggling and it’s going on and off.

When using a PoE switch to power up the camera, you need to make sure that the switch is certified to be used with PoE cameras and that it follows international standards. So, just make sure you’re using the correct PoE switch.

2. Turn off the auto change stream

The Hikvision IP camera or recorder (DVR NVR) uses two types of video stream: main stream and sub-stream. These types of streams depend on the resolution, frame rate and compression type (H.264, H.264+ or H.265) and when the camera auto changes the stream it can cause the picture not to show up.

To fix the Reconnecting.Error Code HCNetSDK.dll[91] error code, open up the iVMS-4200 software, go to Tool and then System Configuration. Access the Image section and untick Auto-change Stream Type (check the picture below).
Hikvision Error Code 91This should the job and you should be able to see your cameras on iVMS-4200 software. If not, to reboot the software, or even your computer.

Ошибка с файлом HCNetSDK появляется при использовании видеорегистратора с несколькими камерами. Часто сбой проявляется в работе только одного записывающего устройства, в то время как остальные функционируют в штатном режиме. Разбираемся с тем, что может быть причиной такого поведения камер.

Ошибки в настройках камеры

При появлении сообщения об ошибке камера перестаёт записывать. Иногда при двойном клике на неё в программе изображение появляется, однако затем снова пропадает. Если ошибка проявляется только на одной или нескольких камерах, а не всех сразу, то пробуем переустановить настройки:

  1. Отключаем кабель питания. 
  2. Зажимаем кнопку Reset.
  3. Подключаем питание обратно (кнопку Reset всё ещё держим).
  4. Ждём, пока камера перезагрузится.
  5. Настраиваем устройство заново. 

Перезагрузка IP-камеры

Сбрасываем настройки камеры и устанавливаем подключение заново

После сброса настроек и повторной установки ошибка не должна повторяться. Если не работает несколько камер, то можно попробовать в программе управления ими включить второй поток. 

Другие возможные причины и способы исправления ошибки

Ошибка с упоминаем HCNetSDK.dll может возникать также по другим причинам. Если сброс параметров и повторная настройка не помогла, то проверяем следующие факторы:

  • Если камера получает питание через POE (Power Over Ethernet) убеждаемся, что источник и устройство поддерживают одинаковые стандарты. Кроме того, источник должен иметь достаточную мощность и не быть перегруженным другими камерами.
  • Проверяем качество витой пары. Разъёмы на обоих концах должны быть правильно обжаты, особенно если используется подключение через POE. 
  • В главном меню изменяем тип потока на автоматический. 

Автоматическое изменение типа поток

Включаем автоматическое изменение типа потока в настройках регистратора

Если проблема носит массовый характер, то может помочь также обновление прошивки. Однако обычно удаётся решить проблему одним из перечисленных выше способов. 

Post Views: 4 357

Файл HCNetSDK.dll считается разновидностью DLL-файла. DLL-файлы, такие как HCNetSDK.dll, по сути являются справочником, хранящим информацию и инструкции для исполняемых файлов (EXE-файлов), например MpSigStub.exe. Данные файлы были созданы для того, чтобы различные программы (например, CMS) имели общий доступ к файлу HCNetSDK.dll для более эффективного распределения памяти, что в свою очередь способствует повышению быстродействия компьютера.

К сожалению, то, что делает файлы DLL настолько удобными и эффективными, также делает их крайне уязвимыми к различного рода проблемам. Если что-то происходит с общим файлом DLL, то он либо пропадает, либо каким-то образом повреждается, вследствие чего может возникать сообщение об ошибке выполнения. Термин «выполнение» говорит сам за себя; имеется в виду, что данные ошибки возникают в момент, когда происходит попытка загрузки файла HCNetSDK.dll — либо при запуске приложения CMS, либо, в некоторых случаях, во время его работы. К числу наиболее распространенных ошибок HCNetSDK.dll относятся:

  • Нарушение прав доступа по адресу — HCNetSDK.dll.
  • Не удается найти HCNetSDK.dll.
  • Не удается найти C:Program Files (x86)NovoSun Technology LimitedSecurity Camera SuiteCyeWebHCNetSDK.dll.
  • Не удается зарегистрировать HCNetSDK.dll.
  • Не удается запустить CMS. Отсутствует требуемый компонент: HCNetSDK.dll. Повторите установку CMS.
  • Не удалось загрузить HCNetSDK.dll.
  • Не удалось запустить приложение, потому что не найден HCNetSDK.dll.
  • Файл HCNetSDK.dll отсутствует или поврежден.
  • Не удалось запустить это приложение, потому что не найден HCNetSDK.dll. Попробуйте переустановить программу, чтобы устранить эту проблему.

Файл HCNetSDK.dll может отсутствовать из-за случайного удаления, быть удаленным другой программой как общий файл (общий с CMS) или быть удаленным в результате заражения вредоносным программным обеспечением. Кроме того, повреждение файла HCNetSDK.dll может быть вызвано отключением питания при загрузке CMS, сбоем системы при загрузке HCNetSDK.dll, наличием плохих секторов на запоминающем устройстве (обычно это основной жесткий диск) или, как нередко бывает, заражением вредоносным программным обеспечением. Таким образом, крайне важно, чтобы антивирус постоянно поддерживался в актуальном состоянии и регулярно проводил сканирование системы.

If you are looking for a solution to fix the Error Code HCNetSDK.dll[91] on your Hikvision camera, don’t look any further. Just read this article…

Hikvision Reconnecting Error Code 91

There are two main reasons to have this issue with your IP camera.

The Hikvision reconnecting Error Code HCNetSDK.dll[91] occurs when there’s no enough power for the camera or when the Auto Change stream type is on. The easiest solution to solve the problem is to use a better PoE power supply and turn the auto change stream off.  

The problem with power

When using PoE (Power Over Ethernet) to power the camera up, is necessary to follow the international standards such as the IEEE 802.3af and IEEE 802.3at to have enough power.

IP camera using PoE

Each one these IEEE standards are designed to have specific voltage (V) and power (W) for the cameras and you need to use the correct power supply to have your camera working properly without some type of error. 

You can use either a PoE switch or a PoE power supply, just ask the vendor a model that follows the IEEE 802.3af standard for fix cameras (dome or bullet) or the IEEE 802.3at standard for PTZ cameras.

Some users and technicians have reported a problem with the message in the iVMS-4200 screen «Reconnecting.Error Code HCNetSDK.dll[91]» due to the lack of power for the camera (when using the wrong PoE power supply).

Just make sure you are using the correct PoE power supply or switch.

To learn more about PoE read the article PoE switch for IP camera

The auto change stream type 

The IP camera or recorder generates a different type of video stream such as main stream and sub stream to send through the network.

Those type of stream can vary according to the resolution, frame rate and compression (such as H.264, H.264+ and H.265) and when the camera changes the stream automatically that can cause some issues.

To prevent the Reconnecting.Error Code HCNetSDK.dll[91] error just open the iVMS-4200 to change the parameter (see the picture below).

Click Tools —> System Configuration

iVMS-4200 System configuration

Just uncheck the Auto-change Stream Type option in the Image Menu

Change the auto stream parameter

This simple change should do the job, now just come back to the main screen and reload the cameras and the error should go away.

Hikvision camera without the error

If some reason the cameras are still not loading properly just restart the iVMS-4500, sometimes a refresh can save the day.

Other factors to consider

If you follow the instruction above everything should work correctly, however, sometimes there are some details that can prevent your camera to work.

Let’s see some extra procedures to help you get rid of the problem.

Infrastructure (cables)

Remember we talked about the use of the correct PoE switch or Power supply to power the camera up? 

Guess what… they send power through cables ! 

If you are not using good quality cables the power or data can be compromised and your system can fail and sometimes even generate the same «Reconnecting.Error Code HCNetSDK.dll[91]»  error.

For IP camera is recommended to use cat5e or cat 6 UTP cables.

UTP cable

Also, make sure the cable are from a good manufacturer such as Furukawa or another brand that is reliable.

You also have to take the distance into consideration, the limitation for UTP cable for data transmission is 100m according to the international standard.

Camera factory default reset

Sometimes a bad configuration or a corrupted configuration file can hold your camera in an error state, so it’s a good practice to reset the device to factory default and reconfigure it from scratch.

Just login into the camera, go to the Upgrade & Maintenance menu.

Click the restore button (see the picture below).

Hikvision DVR factory default

After restoring the camera to factory default configure it manually (don’t import a file with the old configuration).

Firmware upgrade

It’s important to keep all the devices with the last firmware to make sure everything works fine, so take a look at the manufacturer website to see if there’s a new firmware for your device.

You can also go directly to your device menu and click the button to check for the last firmware available.

Hikvision DVR check for new firmware

Conclusion

The Reconnecting.Error Code HCNetSDK.dll[91]» can be eliminated by following the instructions in this article, just make sure to execute each step and if some reason the problem still remains call the Hikvision support.

I hope this article can help you to solve your problem.

Want to learn more ? 

If you want to become a professional CCTV installer or designer, take a look at the material available in the blog. Just click the links below:

Ultimate Guide V3

Please share this information with your friends…

IVMS 4200 Ошибка HCNetSDK.dll

guilty4all Дата: Воскресенье, 04.12.2016, 16:06 | Сообщение # 1

Группа: Проверенные

Репутация: 0

Статус: Offline

Доброго времени суток.
Есть четыре NVR-а  Два 16 канальных и один 32-х канальный.
Была задача вывести это всё дело по сети на комп шефу. Установили IVMS 4200  добавили  туда всё это дело. Всё добавилось . единственная проблема состоит в том что на некоторых NVR-ах в общей сетке отображаются не все камеры в некоторых окошках пишет «Ошибка HCNetSDK.dll» при этом если развернуть камеру на весь экран она показывает. а в общем окне не хочет. На 32-х канальном NVR-е это около 5-ти камер. На самих NVR-ах все камеры отображаются нормально.  Пробовали переустанавливать IVMS -4200 всё осталось так же как и было… Машинка на которой стоит IVMS-ка  это ноутбук ASUS из серии ROG . Подскажите пожалуйста в чём проблема и как её можно устранить?
. Заранее спасибо

 
iTuneDVR Дата: Воскресенье, 04.12.2016, 18:24 | Сообщение # 2

Группа: Проверенные

Репутация: 137

Статус: Offline

Версия iVMS4200?
Конкретную ошибку не пишет в статусной строке внизу? Во всплывающей подсказке?
Шланген до нубука шефа или …. и его ширина?
Скриншот с Панель управления/система и безопасность/Cистема?
Скриншот с диспетчера задач, загрузка ядер?
Скриншот с диспетчера задач, складка сеть в динамике нагрузки?
Кто еще смотрит по сети регистраторы?


Мотивация, направление, посыл ;)
Узнавание паролей Dahua SmartPSS, Hikvision iVMS4200, генерация временного для Uniview. Исследования IT.
www.iTuneDVR.ru

Сообщение отредактировал iTuneDVRВоскресенье, 04.12.2016, 18:47

 
guilty4all Дата: Воскресенье, 04.12.2016, 20:14 | Сообщение # 3

Группа: Проверенные

Репутация: 0

Статус: Offline

Цитата iTuneDVR ()

Версия iVMS4200?Конкретную ошибку не пишет в статусной строке внизу? Во всплывающей подсказке?
Шланген до нубука шефа или …. и его ширина?
Скриншот с Панель управления/система и безопасность/Cистема?
Скриншот с диспетчера задач, загрузка ядер?
Скриншот с диспетчера задач, складка сеть в динамике нагрузки?
Кто еще смотрит по сети регистраторы

В данный момент не могу скинуть скриншоты так как в другом месте. Загрузка ядер около 10 % оперативной памяти примерно 20% либо 25% по показателям самой IVMS. Больше никто не просматривает камеры по сети. Во всплывающей подсказке пишет что типа что не может зацепить поток  ошибка HCNetSDK.dll [91] . Ставил версию 2.4 и версию 2.5 результат одинаковый камеры те же самые в общем окне не показывают. при развороте на большой экран всё работает. все функции доступны.

Добавлено (04.12.2016, 20:14)
———————————————
Свитчи все гигабитные . длинна кабеля из серверной до конечного компа не больше 30 метров. пробовали и прям в серверной запускать IVMS эффекта ноль

 
yuaa2 Дата: Понедельник, 05.12.2016, 09:37 | Сообщение # 4

Группа: Проверенные

Репутация: 24

Статус: Offline

Цитата guilty4all ()

Есть четыре NVR-а  Два 16 канальных и один 32-х канальный.

что-то тут не сходится


Нижний Новгород

 
guilty4all Дата: Понедельник, 05.12.2016, 15:20 | Сообщение # 5

Группа: Проверенные

Репутация: 0

Статус: Offline

Цитатаyuaa2 ()

Цитата guilty4all ()Есть четыре NVR-а  Два 16 канальных и один 32-х канальный.

что-то тут не сходится

Опечаточка)))) Три NVR-а плюс один DVR просто о нём забыл сказать)))
с ним проблем вообще нет))))

 

Установка оборудования видеонаблюдения в Москве и Московской области

yuaa2 Дата: Понедельник, 05.12.2016, 18:15 | Сообщение # 6

Группа: Проверенные

Репутация: 24

Статус: Offline

Камеры у которых ошибка хиквижн? Проверьте как они подключены. Сейчас регистратор просто не воспринимает 2ой поток с них, скорей всего криво подключены или если не хиквижн регистратор просто не умеет подключать 2ой поток с них.


Нижний Новгород

 
guilty4all Дата: Понедельник, 05.12.2016, 19:42 | Сообщение # 7

Группа: Проверенные

Репутация: 0

Статус: Offline

Цитатаyuaa2 ()

Камеры у которых ошибка хиквижн? Проверьте как они подключены. Сейчас регистратор просто не воспринимает 2ой поток с них, скорей всего криво подключены или если не хиквижн регистратор просто не умеет подключать 2ой поток с них.

Вроде как хиквижн… Я заметил разницу в настройках потока у тех камер которые нормально отображаются и  тех которые отображаются с ошибкой. разница именно в битрейте.пробовал менять но что то результата не дало.что странно. интересно какие должны быть стандартные настройки битрейта?

Добавлено (05.12.2016, 19:42)
———————————————
И ещё. как они могут быть добавлены криво если на NVR-ах всё отлично работает… а ошибку выдаёт сама IVMS. Причём добавляю я не каждую камеру по отдельности и а сами NVR-ы. Единственный минус в том что я не смотрел настройки камер в самом  NVR-е

 
yuaa2 Дата: Понедельник, 05.12.2016, 20:18 | Сообщение # 8

Группа: Проверенные

Репутация: 24

Статус: Offline

Цитатаguilty4all ()

Единственный минус в том что я не смотрел настройки камер в самом  NVR-е

там и надо смотреть, нвр перезаписывает настройки, которые вы делаете в камерах, своими


Нижний Новгород

 
guilty4all Дата: Понедельник, 05.12.2016, 20:44 | Сообщение # 9

Группа: Проверенные

Репутация: 0

Статус: Offline

Цитатаyuaa2 ()

там и надо смотреть, нвр перезаписывает настройки, которые вы делаете в камерах, своими

Есть ли какой либо стандарт настроек? от чего отталкиваться… никогда не задавался этим вопросом… так как ранее таких проблем не было.

 
iTuneDVR Дата: Понедельник, 05.12.2016, 22:11 | Сообщение # 10

Группа: Проверенные

Репутация: 137

Статус: Offline

Цитатаguilty4all ()

Во всплывающей подсказке пишет что типа что не может зацепить поток  ошибка HCNetSDK.dll [91] .

Цитатаguilty4all ()

Вроде как хиквижн…

wink


Мотивация, направление, посыл ;)
Узнавание паролей Dahua SmartPSS, Hikvision iVMS4200, генерация временного для Uniview. Исследования IT.
www.iTuneDVR.ru

 

The Hikvision Reconnecting.Error Code HCNetSDK.dll[91] occurs on the iVMS-4200 software and it’s an indication that there’s not enough power juice for the camera or that the Auto-change stream type is enabled.

The fastest solution to solve this issue is to use a better PoE switch and turn the auto-change stream type off. In this guide, you can find steps on how to fix this reconnecting error code issue.
Hikvision Error Code 91

1. Not enough power

This is most likely the main cause of this issue. The camera is not getting enough power juice, it’s struggling and it’s going on and off.

When using a PoE switch to power up the camera, you need to make sure that the switch is certified to be used with PoE cameras and that it follows international standards. So, just make sure you’re using the correct PoE switch.

2. Turn off the auto change stream

The Hikvision IP camera or recorder (DVR NVR) uses two types of video stream: main stream and sub-stream. These types of streams depend on the resolution, frame rate and compression type (H.264, H.264+ or H.265) and when the camera auto changes the stream it can cause the picture not to show up.

To fix the Reconnecting.Error Code HCNetSDK.dll[91] error code, open up the iVMS-4200 software, go to Tool and then System Configuration. Access the Image section and untick Auto-change Stream Type (check the picture below).
Hikvision Error Code 91This should the job and you should be able to see your cameras on iVMS-4200 software. If not, to reboot the software, or even your computer.

Marco Albertini

Marco Albertini was born in Italy and spent his formative years surrounded by the beauty and history of Europe. After completing his studies in Computer Science, he developed a passion for security camera systems, alarms, and cloud services.

In 2010, Marco decided to pursue his career in New York and has been living there ever since. His extensive knowledge and experience have made him a sought-after expert in his field, and he has helped countless businesses and homeowners secure their properties with advanced security solutions.

22.5.20

The Hikvision reconnecting Error Code HCNetSDK. dll[91]





The Hikvision reconnecting Error Code HCNetSDK.dll[91] occurs when there’s no enough power for the camera or when the Auto Change stream type is on.


The easiest solution to solve the problem is to use a better PoE power supply and turn the auto change stream off.


*************************


Posted by

nim




at

10:36 AM





No comments:

Post a Comment


Newer Post


Older Post

Home

Subscribe to:
Post Comments (Atom)

  • Не удалось подписать документ ошибка исполнения функции
  • Не удалось подключиться неизвестная ошибка ark
  • Не удалось подключиться к удаленному рабочему столу так как на нем произошла ошибка
  • Не удалось подключиться к удаленному компьютеру так как на нем произошла ошибка
  • Не удалось подключиться к удаленному компьютеру код ошибки 0х204